H3DK-HBL AC/DC24-48 Omron, H3DK-HBL AC/DC24-48 Datasheet - Page 12

no-image

H3DK-HBL AC/DC24-48

Manufacturer Part Number
H3DK-HBL AC/DC24-48
Description
TIMER, POWER OFF DELAY, 120S, 24AC/DC
Manufacturer
Omron
Datasheet

Specifications of H3DK-HBL AC/DC24-48

Contact Configuration
SPDT
Delay Time Range
1s To 120s
Relay Mounting
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Adjustment Type
Screwdriver Slot
Contact Current Ac Max
5A
Contact Current Dc
RoHS Compliant
12
H3DK-F
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity
*5. 125 VDC: 0.15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
■ Characteristics
■ Applicable standards
■ I/O
Accuracy of operating
time
Setting error
Influence of voltage
Influence of tempera-
ture
Insulation resistance
Dielectric strength
Impulse withstand volt-
age
Noise immunity
Static immunity
Vibration
resistance
Shock re-
sistance
Life ex-
pectancy
Degree of protection
Weight
Safety standards
EMC
Input
Output
power supply to the Timer with device with a solid-state output, such as a sensor.
(Reference Values) on the next page.
Minimum load: 10 mA at 5 VDC (P level, reference value)
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Destruction 1,000 m/s
Malfunction 100 m/s
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
(EMI)
Radiated Emissions:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuations and Flicker: EN61000-3-3
(EMS)
ESD Immunity:
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
Burst Immunity:
Surge Immunity:
Control output
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
±10% of FS ±0.05 s max.
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
24 to 240 VAC/VDC: 3 kV between power terminals, 4.5 kV between current-
carrying metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV between power terminals, 1.5 kV between current-carrying metal
parts and exposed non-current-carrying metal parts
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
Malfunction: 4 kV, Destruction: 8 kV
IP30 (Terminal block: IP20)
Approx. 110 g
100 MΩ min. at 500 VDC
1-ns rise): ±1.5 kV
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
2
3 times each in 6 directions
2
3 times each in 6 directions
Output is turned ON/OFF according to the time set on the ON
time setting dial and OFF time setting dial.
EN61812-1
EN 55011 class B
EN 55011 class B
EN 61000-3-2
EN61812-1
EN 61000-4-2: 6 kV contact discharge,
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
EN 61000-4-4: 2 kV power line,
EN 61000-4-5: 2 kV common mode,
8 kV air discharge
1 kV I/O signal line
1 kV differential mode
None
● Installation Pitch and Output
The relation between the installation pitch
and the load current is shown in the follow-
ing graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
Testing Method
Tested Timer: H3DK-F
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
DIN Track
Switching Capacity (Reference
Values)
80
70
60
50
40
30
20
10
timer
0
Test
1
Timer installation pitch: d
1
timer
Test
2
2
timer
Test
3
3
timer
Test
4
4
Load current (A)
timer
Test
5
5
d = 50 mm
d = 10 mm
d = 5 mm
d = 0 mm
6