H3DK-HBL AC/DC24-48 Omron, H3DK-HBL AC/DC24-48 Datasheet - Page 22

no-image

H3DK-HBL AC/DC24-48

Manufacturer Part Number
H3DK-HBL AC/DC24-48
Description
TIMER, POWER OFF DELAY, 120S, 24AC/DC
Manufacturer
Omron
Datasheet

Specifications of H3DK-HBL AC/DC24-48

Contact Configuration
SPDT
Delay Time Range
1s To 120s
Relay Mounting
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Adjustment Type
Screwdriver Slot
Contact Current Ac Max
5A
Contact Current Dc
RoHS Compliant
22
H3DK-H
*1. DC ripple: 20% max. (A single-phase, full-wave rectifying power supply can be connected.)
*2. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*3. The control output ratings are for one H3DK operating alone.
■ Characteristics
■ Applicable standards
■ I/O
Accuracy of operating
time
Setting error
Influence of voltage
Influence of tempera-
ture
Insulation resistance
Dielectric strength
Impulse withstand volt-
age
Noise immunity
Static immunity
Vibration
resistance
Shock re-
sistance
Life ex-
pectancy
Degree of protection
Weight
Safety standards
EMC
Input
Output
If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity (Reference Values) on the next page.
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Destruction 1,000 m/s
Malfunction 100 m/s
Mechanical 10 million operations min. (under no load at 1,200 operations/h)
Electrical
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
(EMI)EN61812-1
Radiated Emissions:EN 55011 class B
Emission AC Mains:EN 55011 class B
Harmonic Current:EN 61000-3-2
Voltage Fluctuations and Flicker:EN61000-3-3
(EMS)EN61812-1
ESD Immunity:EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:EN 61000-4-5: 2 kV common mode,
1 kV differential mode
Control output
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
±10% of FS ±0.05 s max.
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
Between power supply terminals: 1 kV for 24-VAC/DC and 48-VAC/DC models,
3 kV for all other models.
Between current-carrying metal parts and exposed non-current-carrying metal
parts): 1.5 kV for 24-VAC/DC and 48-VAC/DC models, 4.5 kV for all other
models.
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
Malfunction: 4 kV, Destruction: 8 kV
IP30 (Terminal block: IP20)
Approx. 120 g
100 MΩ min. at 500 VDC
1-ns rise): ±1.5 kV (between power supply terminals)
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
2
3 times each in 6 directions
2
3 times each in 6 directions
The Timer operates as soon as the Timer is turned ON. The
Timer starts timing when the power is turned OFF and the output
is turned OFF when the time set on the dial elapses.
None
● Installation Pitch and Output
The relation between the installation pitch
and the load current is shown in the fol-
lowing graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
Testing Method
Tested Timer: H3DK-H
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
DIN Track
Switching Capacity (Reference
Values)
80
70
60
50
40
30
20
10
timer
0
Test
1
Timer installation pitch: d
1
timer
Test
2
2
timer
Test
3
3
timer
Test
4
4
Load current (A)
timer
Test
5
5
d = 50 mm
d = 10 mm
d = 5 mm
d = 0 mm
6

Related parts for H3DK-HBL AC/DC24-48