E5ER-CT3DW-FLK AC/DC24 Omron, E5ER-CT3DW-FLK AC/DC24 Datasheet - Page 5

no-image

E5ER-CT3DW-FLK AC/DC24

Manufacturer Part Number
E5ER-CT3DW-FLK AC/DC24
Description
CONTROLLER DIGITAL RS-485 24V
Manufacturer
Omron
Series
E5ERr
Type
Digital Controllerr
Datasheet

Specifications of E5ER-CT3DW-FLK AC/DC24

Input Type
Current, Voltage, RTD, Thermocouple (Multiple)
Controller Type
On/Off
Temperature Range
Selectable, Varies By Input Type
Output Type
Current
Supply Voltage
24VAC/DC
Size
48mm W x 96mm H (1/8 DIN)
Communications
RS-485 (CompoWay/F)
Display Type
LCD; 5 Digit (2), 3 Digit
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Features
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E5ER-CT3DW-FLKAC/DC24
E5ERCT3DWFLKACDC24
■ Characteristics
Note: 1. K-, T-, or N-type thermocouple at −100°C max.: ±2°C ±1 digit max.
Indication accuracy
Control mode
Influence of temperature
Influence of temperature
Control period
Proportional band (P)
Integral time (I)
Derivative time (D)
Hysteresis
Manual reset value
Alarm setting range
Input sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Inrush current
Weight
Degree of protection
Memory protection
Applicable standards
EMC
2. U- or L-type thermocouple: ±1°C ±1 digit
3. “EU” (Engineering Unit) represents the unit after scaling. If a temperature sensor is used it is either °C or °F.
4. Conditions: Ambient temperature from −10 to 23 to 55°C and voltage of −15% to 10% of rated voltage.
U- or L-type thermocouple: ±2°C ±1 digit max.
B-type thermocouple at 400°C max.: No accuracy specification.
R- or S-type thermocouple at 200°C max.: ±3°C ±1 digit max.
W-type thermocouple: (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
R- or S-type thermocouple at 200°C max.: ±1.5°C ±1 digit
Thermocouple input with cold junction compensation: (±0.1% of PV or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Thermocouple input without cold junction compensation: (±0.1% FS or ±1°C, whichever is smaller) ±1 digit (See note 2.)
Analog input: ±0.1% FS ±1 digit max.
Platinum resistance thermometer input: (±0.1% of PV or ±0.5°C, whichever is greater) ±1 digit max.
Position-proportional potentiometer input: ±5% FS ±1 digit max.
Standard control (heating or cooling control), heating/cooling control, standard control with remote SP (2-input models only), heating/cool-
ing control with remote SP (2-input models only), cascade standard control (2-input models only), cascade heating/cooling control (2-input
models only), proportional control (2-input models only), position-proportional control (control-valve control models only)
Thermocouple input (R, S, B, W): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
∗K-type thermocouple at −100°C max.: ±10°C max.
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
0.2 to 99.0 s (in units of 0.1 s) for time-proportioning control output
0.00% to 999.99% FS (in units of 0.01% FS)
0.0 to 3,999.9 s (in units of 0.1 s)
0.0 to 3,999.9 s (in units of 0.1 s)
0.01% to 99.99% FS (in units of 0.01% FS)
0.0% to 100.0% (in units of 0.1% FS)
−19,999 to 99,999 EU (See note 3.) (The decimal point position depends on the input type and the decimal point position setting.)
50 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between charged terminals of different polarities)
10 to 55 Hz, 20 m/s
100 m/s
100 to 240-VAC models: 50 A max.
24 VAC/VDC models: 30 A max.
Controller only: Approx. 330 g; Mounting bracket: Approx. 60 g; Terminal cover: Approx. 16 g
Front panel: NEMA4X for indoor use (equivalent to IP66); Rear case: IP20; Terminals: IP00
Non-volatile memory (number of writes: 100,000)
UL61010C-1, CSA C22.2 No. 1010-1
EN61010-1 (IEC61010-1): Pollution degree 2/overvoltage category 2
EMI: EN61326
EMS: EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1 Class A
Noise Terminal Voltage: EN55011 Group 1 Class A
ESD Immunity: EN61000-4-2:
Electromagnetic Immunity: EN61000-4-3:
Burst Noise Immunity: EN61000-4-4:
Conducted Disturbance Immunity: EN61000-4-6:
Surge Immunity: EN61000-4-5:
Power Frequency Magnetic Field Immunity: EN61000-4-8: 30 A/m (50 Hz) continuous field
Voltage Dip/Interrupting Immunity: EN61000-4-11:
2
, 3 times each in X, Y, and Z directions
2
for 10 min each in X, Y, and Z directions
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (amplitude-modulated, 80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3)
2 kV power line (level 3)
2 kV output line (relay output) (level 4)
1 kV measurement line, I/O signal line (level 4)
1 kV communications line (level 3)
3 V (0.15 to 80 MHz) (level 3)
1 kV line to line (power line, output line (relay output)) (level 2)
2 kV line to ground (power line, output line (relay output)) (level 3)
0.5 cycle, 100% (rated voltage)
E5ER