E5ZE-8AQHD1PB-V2 DC24 Omron, E5ZE-8AQHD1PB-V2 DC24 Datasheet - Page 2

no-image

E5ZE-8AQHD1PB-V2 DC24

Manufacturer Part Number
E5ZE-8AQHD1PB-V2 DC24
Description
CONTROLLR TEMP 24V RES THRMOMETR
Manufacturer
Omron
Series
E5ZEr
Type
Temperature Controller, Multipointr
Datasheet

Specifications of E5ZE-8AQHD1PB-V2 DC24

Input Type
RTD
Controller Type
Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Output Type
Voltage
Supply Voltage
24VDC
Size
65mm W x 243mm H
Display Type
Separate Display Available
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Features
-
Communications
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E5ZE-8AQHD1PB-V2DC24
E5ZE8AQHD1PBV2DC24
Temperature Ranges
Note: 1. The factory setting is 0 (Type K for thermocouple input or Pt100 for platinum resistance thermometer input.)
Specifications
J TEMPERATURE CONTROLLER
Ratings
230
E5ZE-8jD1jB
Input
Thermocouple
Platinum resistance
thermometer
Rated voltage
Permissible voltage fluctuation
Power consumption
Analog
inputs
Control
outputs
Alarm outputs
Number of inputs
Setting method
Control method
Memory bank input
Memory bank designation inputs
Ambient temperature
Ambient humidity
2. Platinel is a registered trademark of Englehard Industries.
Inputs
Input impedance
Rated current
Voltage output
(with short-circuit protection)
Current output
Open-collector NPN output
(cooling only)
K (CA)
J (IC)
R
S
T (CC)
E (CRC)
B
N
L
U
W
PL II
Pt100
JPt100
2
Temperature range
–200 _C to 1,300_C
–100 _C to 850_C
0_C to 1,700_C
0_C to 1,700_C
–200 _C to 400_C
0_C to 600_C
100_C to 1,800_C
0_C to 1,300_C
–100 _C to 850_C
–200 _C to 400_C
0_C to 2,300_C
0_C to 1,300_C
–100.0 _C to 500.0_C
–100.0 _C to 500.0_C
24 VDC
85 to 110% of rated voltage
15 W +20% max. at 24 V DC
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, and PL II
Platinum resistance thermometer: JPt 100, Pt 100
Thermocouple: 1 MΩ min.
Platinum resistance thermometer: 1 mA
ON voltage: 12 ±1.2 VDC
OFF voltage: 0.5 VDC max.
Max. load current: 30 mA/output
Rated output range: 4 to 20 mA (4 +0/–0.6 mA for 0% output, 20 +2/–0 mA for 100% output)
Max. load resistance: 600 Ω/output
Max. voltage: 30 VDC
Max. load current: 50 mA/output
Residual voltage when ON: 2 VDC max.
Leakage current when OFF: 1 mA max.
Temperature alarms: Two outputs: alarm 1 and alarm 2 for all outputs in each word.
HB alarm (heater burnout detection): One output for all outputs in each word.
HS alarm (SSR fault detection): One output for all outputs in each word.
Temperature controller error output (memory, set value, or hardware error): One output
All outputs are NPN open-collector outputs with a max. voltage of 30 VDC and max. load
current of 50 mA/output.
8 input points and 8 control points
Set by communications
ON/OFF, hybrid of advanced PID and fuzzy logic control, or manual operation
8 points for each control point
Designated through communication or memory bank designation input
With contact signal input:
With non-contact signal input: ON residual voltage:
Operating: 0°C to 55°C (32°F to 131°F) with no icing or condensation
Storage: –25°C to 65°C (–14°F to 149°F) with no icing or condensation
Operating: 35% to 85% RH
–300 _F to 2,300_F
–100 _F to 1,500_F
0_F to 3,000_F
0_F to 3,000_F
–300 _F to 700_F
0_F to 1,100_F
300_F to 3,000_F
0_F to 2,300_F
–100 _F to 1,500_F
–300 _F to 700_F
32_F to 4,100_F
0_F to 2,300_F
–100.0 _F to 900.0_F
–100.0 _F to 900.0_F
ON short–circuit resistance:
OFF open resistance:
OFF leakage current:
Setting (See Note 1)
0
1
2
3
4
5
6
7
8
9
A
B
0
1
100 kΩ min.
1 mA DC max.
1 kΩ max.
2 VDC max.
E5ZE-8jD1jB
1_C or 0.1_C
Minimum units