CP2000AC54PE Lineage Power, CP2000AC54PE Datasheet
CP2000AC54PE
Specifications of CP2000AC54PE
Related parts for CP2000AC54PE
CP2000AC54PE Summary of contents
Page 1
... This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.) ** ISO is a registered trademark of the International Organization of Standards. *** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3. Compact Power Line Features • ...
Page 2
... Output Voltage Setpoint Setpoint Accuracy -1 Overall Regulation -2 Output Voltage Margin 44 42 Maximum Output Current Current Share Lineage Power CP2000AC54 Front-End Power Supply Typ Max Units Notes The power supply automatically configures its 85 operating mode based on the voltage level it 175 reads on first turn ON. (This information is retained as long as internal bias is maintained ...
Page 3
... Output Voltage Setpoint Output Current Overall Regulation Ripple and Noise Over-voltage Clamp Over-current Limit Physical Length (in./mm) Width (in./mm) Height (in./mm) Weight (lb/kg) Lineage Power CP2000AC54 Front-End Power Supply Typ Max Units Notes 250 mVrms Measured with 20MHz bandwidth under any 500 mVpk-pk condition of loading ...
Page 4
... Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the cable. See the figure below. 4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode capacitors that assist in meeting compliance. ...
Page 5
... Data Sheet Status and Control The rectifier provides three means for monitor/control: analog, PMBus compliant I RS485 for interfacing to Lineage Power controllers or battery plants. Details of analog controls are provided in this data sheet under Signal Definitions. Lineage Power will provide separate application notes on PMBus protocol for users to interface to the CPL rectifiers ...
Page 6
... Connector is viewed from the rear positioned inside the power supply. Signal pins columns 1 and 2 are referenced to 54_OUT (-DC). Signal pins columns 3 through 6 are referenced to Logic GRD. Last-to-make first-to-break pins. First-to-make last-to-break longest pin implemented in the mating connector. Lineage Power CP2000AC54 Front-End Power Supply Power Supply LED State ...
Page 7
... All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals should be pulled HI to either 3.3V or 5V. Maximum sink current 5mA. An active LO signal (< 0.4Vdc). All signals are referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative for more details. ...
Page 8
... Dimensions 4.00 in. (101.6 mm) Ordering Information Item Description CP2000AC54PE Designed to IEEE802.3 POE compliance, RoHS 5/6 CP2000AC54PEZ Tested to IEEE802.3 POE compliance, RoHS 6/6 World Wide Headquarters Lineage Power LLC 601 Shiloh Road, Plano, TX 75074, USA +1-800-526-7819 (Outside U.S.A.: +1-972-284-2626) www.lineagepower.com e-mail: techsupport1@lineagepower.com Lineage Power reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s) or information. © ...