E2E2-X5B1-M1 Omron Automation, E2E2-X5B1-M1 Datasheet - Page 2

no-image

E2E2-X5B1-M1

Manufacturer Part Number
E2E2-X5B1-M1
Description
Sensor, Proximity; 29 mm; 12 to 24 VDC; 13 mA (Max.); Shielded; 0.6 kHz;
Manufacturer
Omron Automation
Type
Inductiver
Datasheet

Specifications of E2E2-X5B1-M1

Body Style
Cylindrical
Current, Consumption
13 mA (Max.)
Dimensions
75 mm L
Frequency, Switching
0.6 kHz
Function
Proximity
Material, Housing
Nickel-Plated Brass (Barrel)
Output
PNP
Primary Type
Proximity
Standards
CE Marked
Technology
Inductive
Temperature, Ambient, Maximum
85 °C
Temperature, Ambient, Minimum
-40 °C
Voltage, Supply
12-24 VDC
Supply Voltage Range
10-55 VDC or 20-264 VAC, 50/60 Hz (Model Dependant)
Load Rating
200 mA (DC) or 5-200 mA/5-300 mA (AC) (Model Dependant)
Approvals
CE, UL, CSA (Model Dependant)
Lead Free Status / Rohs Status
RoHS Compliant part
J ACCESSORIES
J REPLACEMENT PARTS
Specifications
E2E2 3-Wire DC
Description
Mounting brackets
Silicone rubber covers for shielded sensors
Connector cordsets
Description
Mounting hardware including one pair of
metal nuts and one washer
Part number
Size
Type
Sensing distance
Supply voltage
(operating voltage
range)
Current consumption
Sensing object
Setting distance
Standard object
(mild steel)
Differential travel
Response frequency
Operation (with sensing
object approaching)
Control output
(switching capacity)
Circuit protection
Indicator
Ambient
temperature
Ambient
humidity
Temperature influence
Voltage influence
Residual voltage
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Operating
Operating
E2E2-X2Cj/Bj
M12
Shielded
2 mm (0.08 in)
±10%
12 to 24 VDC, ripple (p-p): 10% max., (10 to 55 VDC)
13 mA max.
Magnetic metals (refer to Engineering Data for non-magnetic metals)
0 to 1.6 mm
(0 to 0.06 in)
12 x 12 x
1 mm (0.47 x
0.47 x 0.04 in)
10% max. of sensing distance
1.5 kHz
B1/C1 models: Load ON
B2/C2 models: Load OFF
200 mA max., open collector
Reverse connection protection, surge absorber, load short-circuit protection
Operation indicator (red LED)
- -40°C to 85°C (- -40°F to 185°F) with no icing
35% to 95%
±15% max. of sensing distance at 23°C in temperature range of - -40°C to 85°C (- -40°F to 185°F)
±10% max. of sensing distance at 23°C in temperature range of - -25°C to 70°C (- -13°F to 158°F)
±1% max. of sensing distance in rated voltage range ±15%
2.0 V max. (under load current of 200 mA with cable length of 2 m)
50 MΩ min. (at 500 VDC) between current carry parts and case
1,000 VAC for 1 min between current carry parts and case
10 to 55 Hz, 1.5-mm double amplitude for 10 times each in X, Y, and Z axes
1,000 m/s
2
(approx. 100G) for 10 times each in X, Y, and Z axes
E2E2-X5MCj/Bj
Unshielded
5 mm (0.20 in)
±10%
0 to 4.0 mm
(0 to 0.16 in)
15 x 15 x 1 mm
(0.59 x 0.59 x
0.04 in)
0.4 kHz
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
See Y96E Connector Cordsets data sheet for details
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
(This table continues on the next page.)
E2E2-X5Cj/Bj
M18
Shielded
5 mm (0.20 in)
±10%
0 to 4.0 mm
(0 to 0.16 in)
18 x 18 x
1 mm (0.71 x
0.71 x 0.04 in)
0.6 kHz
3
E2E2-X10MCj/Bj
Unshielded
10 mm (0.39 in)
±10%
0 to 8.0 mm
(0 to 0.31 in)
30 x 30 x 1 mm
(1.18 x 1.18 x
0.04 in)
0.2 kHz
Part number
Y92E-B12
Y92E-B18
Y92E-B30
Y92E-E12-2
Y92E-E18-2
Y92E-E30-2
Part number
M12-MHWS
M18-MHWS
M30-MHWS
E2E2-X10Cj/Bj
M30
Shielded
10 mm (0.39 in)
±10%
0 to 8.0 mm
(0 to 0.31 in)
30 x 30 x 1 mm
(1.18 x 1.18 x
0.04 in)
0.4 kHz
E2E2 3-Wire DC
E2E2-X18MCj/Bj
Unshielded
18 mm (0.71 in)
±10%
0 to 14.0 mm
(0 to 0.55 in)
54 x 54 x 1 mm
(2.13 x 2.13 x
0.04 in)
0.1 kHz

Related parts for E2E2-X5B1-M1