• 90 -264 Vac nominal input range
• Overvoltage, over temp. and short circuit protection
• Approved to UL, CSA and EN Standards
• Power Good LED
• Low Leakage
• 12 V Auxiliary output
• Medical and commercial approvals
The GPMP Series are universal input AC/DC power supplies with power
factor correction (PFC) with up to 900 Watts ouput power. The GPMP
product incorporates true inhibit, power fail alarm, power good signal and
fan control. The series is approved to EN60601-1 and EN60950-1 to reduce
design-in time and end system compliance costs
All specifications are typical at nominal input, full load at 25
Page 1 of 3
High Power Supplies 900 Watt AC/DC Universal Input Power Supply
OUPUT SPECIFICATIONS
Output Power
Total Regulation
Rise time
Transient response
Temperature Coef-
ficient
Overvoltage protection
Short Circuit protection
EMC INFORMATION
Conducted emissions
Radiated emissions
Line freq. harmonics
Voltage fluctuations
ESD Air
ESD Contact
Radiated immunity
Fast Transients (EFT)
Line surge immunity
Conducted immunity
Power freq. mag. field
Voltage dip immunity
Integral forced air
At turn-on
Main output 25%
0.2 A/ms
block wall
EN55011
EN55011
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Level B
Level A
Class A
Complies (clause 5b)
8 kV contact
6 kV air
3 V/m
2 kV 5 kHz
1 kV diff /2 kV cm
3 Vrms
3 A/m
Unit will ride through without loss of
output at 75% of rated load with AC
power fail warning.
900 Watts max.
See table
3.0 s max.
3.5% max. dev. 350 ms recovery
to 1%
+/-0.03%/oC
125% +/-10%
Yes
GPMP900 SERIES
O
C unless otherwise stated
ENVIRONMENTAL SPECIFICATIONS
Thermal Performance
Maximum Altitude
Relative Humidity
Vibration (operating)
Vibration (non-operating)
Shock
Shock
INPUT SPECIFICATIONS
Input Voltage range
Input frequency
Input surge current
Ground Leakage current
Input current
Input current
Input fuse
SINGLE OUTPUT MEDICAL POWER SUPPLY
g
Universal input
264 Vac 60 Hz
115 Vac
230 Vac
F1
operating ambient
(see ratings chart)
non-operating
0 - 50
Fan cooled
operating / non-operating
non-condensing
0.003 g
0.026 g
half-sine 20 g
half-sine 40 g
o
C
2
2
/Hz
/Hz
pk
pk
SPECIFICATIONS
100-240 nom (90 - 264 max)
Vac
47 Hz to 63 Hz
40 A max.
160 mA
12.0 A max
6.0 A max
15.0 A
-20
-40 to +85
900 Watts
10,000 ft. / 40,000
ft. max.
5% - 90% RH
1.5 g
min/axis
5.0 g
hr/axis
10 ms, 3 axes, 6
shocks total
10 ms, 3 axes, 6
shocks total
SUMMARY
o
C to +70
rms
rms
3 axes 10
3 axes, 1
o
C
o
C