Specifications of S8TS-06024F-E1

Brand/series
S8TS Series
Configuration
Enclosed
Current, Inrush
50 A (Max.)
Current, Rating
2.5 A
Diameter
5 mm
Frequency
50⁄60 Hz
Height
4.72 in.
Mounting Type
DIN Rail
Number Of Outputs
1
Operation
Switching
Output
24 VDC @ 2.5 A
Power, Output
60 W
Primary Type
AC-DC
Temperature, Operating, Maximum
+65 °C (Ambient)
Temperature, Operating, Minimum
-25 °C (Ambient)
Voltage, Input
100 to 240 VAC
Voltage, Output
24 VDC
Voltage, Rating
24 V
Width
1.69 in.
Lead Free Status / Rohs Status
RoHS Compliant part
Block-type Switch Mode Power Supply That
Mounts to DIN Rail
• One model covers 30 to 120 W (12-V models).
• One model covers 60 to 240 W (24-V models).
• Easy creation of multi-power supply configurations with different
• Improve power supply system reliability by creating N+1 redun-
• RoHS-compliant
Model Number Structure
■ Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative.
■ List of Models
Basic Block
Bus Line Connector
Note: 1. One S8T-BUS01 Connector and one S8T-BUS02 Connector are included as accessories.
1. Capacity
S8TS-@@@@@@-@@
5 V
12 V
24 V
Connector with DC line connected
(For parallel operation)
Connector with DC line not connected
(Not for parallel operation)
output power supplies connected together (5-V, 12-V, and 24-V
models).
dant systems (12-V and 24-V models).
Switch Mode Power Supply
S8TS
!
025: 25 W
030: 30 W
060: 60 W
Output voltage
2. Bus Line Connectors are ordered separately. When connecting Power Supplies with Bus Line Connectors, order the Bus Line Connectors
3. Attached connectors: 2ESDPLM-05P (for output terminal) and 3ESDPLM-03P (for input terminal) made by DINKLE ENTERPRISE.
4. One package contains 10 S8T-BUS01 Connectors.
5. One package contains 10 S8T-BUS02 Connectors.
Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 12.
separately.
1
Specifications
2
3
2. Output Voltage
05:
12:
24:
5 A
2.5 A
2.5 A
4
Output current
5 V
12 V
24 V
3. Structure
---
S8TS-03012-E1
S8TS-06024-E1
None: Screw terminals
F:
1 Connector
10 Connectors (See note 4.)
1 Connector
10 Connectors (See note 5.)
With Bus Line
(See note 1.)
Connectors
Connector terminals
Screw terminal Model
Number of Connectors
S8TS-02505
S8TS-03012
S8TS-06024
Without Bus Line
(See note 2.)
Connectors
4. Bus Line Connectors
None: Basic Block only
E1:
---
S8TS-03012F-E1
S8TS-06024F-E1
S8T-BUS01
S8T-BUS11
S8T-BUS02
S8T-BUS12
Connector terminal Model (See note 3.)
One S8T-BUS01 and one S8T-BUS02
included as accessories
With Bus Line
(See note 1.)
Connectors
Model number
CSM_S8TS_DS_E_2_1
S8TS-02505F
S8TS-03012F
S8TS-06024F
Without Bus Line
(See note 2.)
Connectors
1

Related parts for S8TS-06024F-E1

S8TS-06024F-E1 Summary of contents

Page 1

... Connectors (See note 4.) 1 Connector 10 Connectors (See note 5.) CSM_S8TS_DS_E_2_1 One S8T-BUS01 and one S8T-BUS02 included as accessories Connector terminal Model (See note 3.) With Bus Line Without Bus Line Connectors Connectors (See note 1.) (See note 2.) --- S8TS-02505F S8TS-03012F-E1 S8TS-03012F S8TS-06024F-E1 S8TS-06024F Model number S8T-BUS01 S8T-BUS11 S8T-BUS02 S8T-BUS12 1 ...

Page 2

... Specifications ■ Ratings/Characteristics 12/24-V Models (Basic Block: S8TS-06024@/S8TS-03012@) Item Efficiency (TYP.) Input Voltage (See note 1.) Frequency (See note 1.) Current 100 V input 200 V input Power factor Harmonic current emissions Leakage current 100 V input 240 V input Inrush current 100 V input (See note 5.) ...

Page 3

... Models (Basic Block: S8TS-02505@) Item Efficiency (typical) Input Voltage (See note 1.) Frequency (See note 1.) Current 100 V input 200 V input Power factor Harmonic current emissions Leakage current 100 V input 240 V input Inrush current 100 V input (See note 5.) 200 V input Output Voltage adjustment range ...

Page 4

... Connections ■ Block Diagrams S8TS-06024@ and S8TS-03012@ AC (L) Fuse Noise 2.0 A filter INPUT AC (N) Rectifier Connected to Bus Line Connector S8TS-02505@ AC(L) Fuse Noise 2.0 A filter INPUT AC(N) Rectifier Connected to Bus Line Connector Inrush Harmonic Smooth- Rectifier and current current ing smoothing ...

Page 5

... S8T-BUS02 Bus Line Connector Input Terminal ( Input Terminal (N) C Protective Earth (PE) Terminal ( ) D Parallel Operation Signal Terminal E DC Output Terminal (+ Output Terminal (−V) G Selector H Connection Status Indicator S8TS INPUT 50/60Hz AC100 -240V 1. S8TS-06024F POWER SUPPLY + Class2 Power Supply DC LOW OUTPUT V.ADJ DC24V 2. LOW ...

Page 6

... For the current balance function to operate, the S8T- BUS01 must be used. Not Using Parallel Operation Use the S8T-BUS02 (DC line not connected). (See Figure 2.) S8T-BUS01 −V+V Figure 1: DC line connected (parallel connection) S8TS 180 W 240 W 3 blocks 4 blocks AC input 120 Selector ...

Page 7

... Basic Block, not all the Blocks. Series Operation and ± Output Using 2 Basic Blocks enables series operation and the use of ± output. An external diode is not required for S8TS-06024@ and S8TS-03012@ models, but is required for S8TS-02505@ models. Use the following as a rough guide for selecting the diode. ...

Page 8

... Models Rated output voltage The values shown in the above diagrams are for reference only. Note: Do not turn ON the input power again until the cause of the overvoltage has been removed. S8TS N+1 Redundant System 0 −20 − Ambient temperature (°C) Overvoltage ...

Page 9

... ON residual voltage max. OFF leakage current: 0.1 mA max. 3. The indicators become dimmer as the output voltage approaches 0 V. Undervoltage Detection Output Blocks with Screw Terminals DC LOW OUT −V S8TS Voltage status Output status (See note 2.) Approx. 80% ON min. of the rated output voltage Approx ...

Page 10

... Eight, M4 pan-head 1 screw 35.5 35.5 50 1.8 11.5 1 spring washer 4.8 S8TS LOCK 4 35 120 LOCK 4 35 120 7.3± 0.15 35± 27± 0.3 0.15 15(5)* 1 *Values in parentheses are for the PFP-50N. 16 35± 1.5 10 ...

Page 11

... S8TS. Just link Basic Blocks for redundant operation in parallel to enable N+1 redundant operation. A current balance function is used for S8TS N+1 redundant operation so that each Block provides the same current. If one Power Supply fails, the remaining Power Supplies share the load of the failed Power Supply, and operation continues with each Power Supply providing more current ...

Page 12

... Be sure to remove the sheet covering the Power Supply for machining before turning ON the power so that it does not interfere with heat dissipation. Use the following material for the wires to be connected to the S8TS to prevent smoking or ignition caused by abnormal loads. Recommended Wire Size for Single-unit ...

Page 13

... Buzzing Noise When the Input Is Turned ON A harmonic current suppression circuit is built into the input power. This circuit can create noise when the input is turned ON, but it will last only until the internal operation stabilizes and does not indicate any problem in the Power Supply. S8TS 13 ...