S8TS-06024F-E1 Omron Automation, S8TS-06024F-E1 Datasheet - Page 6

no-image

S8TS-06024F-E1

Manufacturer Part Number
S8TS-06024F-E1
Description
Power Supply; 24 V; 2.5 A; 50/60 Hz; 50 A (Max.); 1.69 in.; 4.72 in.; 5 mm
Manufacturer
Omron Automation
Datasheet

Specifications of S8TS-06024F-E1

Brand/series
S8TS Series
Configuration
Enclosed
Current, Inrush
50 A (Max.)
Current, Rating
2.5 A
Diameter
5 mm
Frequency
50⁄60 Hz
Height
4.72 in.
Mounting Type
DIN Rail
Number Of Outputs
1
Operation
Switching
Output
24 VDC @ 2.5 A
Power, Output
60 W
Primary Type
AC-DC
Temperature, Operating, Maximum
+65 °C (Ambient)
Temperature, Operating, Minimum
-25 °C (Ambient)
Voltage, Input
100 to 240 VAC
Voltage, Output
24 VDC
Voltage, Rating
24 V
Width
1.69 in.
Lead Free Status / Rohs Status
RoHS Compliant part
Operation
■ Application Methods
Increasing Output Capacity
Example for 24-V Models
Configuring Multiple Outputs
Maximum Number of Blocks That Can
Be Linked
Basic Blocks can be linked using Bus Line Connectors.
Increasing Output Capacity
N+1 Redundant Systems
To ensure stable operation when there is a failure in one of the
Blocks, use within the derating curve for N+1 redundant systems.
Multi-output Power Supply
Up to 4 Basic Blocks with different output voltage specifications can
be linked.
Selecting Bus Line Connectors
Select Bus Line Connectors according to the linking method as
follows:
Block Power Supply
S8TS-02505@
S8TS-03012@
S8TS-06024@
Models
S8T-BUS01
Connector
Bus Line
No
Up to 4 Blocks
Up to 4 Blocks
Number of Blocks N+1 Redundant System
60 W
24 V
Block Power Supply
S8T-BUS01
BUS01
+V
L
N
-V
No
Up to 5 Blocks
Up to 5 Blocks
60 W
24 V
Capacity
Number
Output
Blocks
S8T-BUS02
of
BUS02
L
N
30 W
12 V
1 block
60 W
Using Parallel Operation
Use the S8T-BUS01 (DC line connected). (See Figure 1.)
The S8T-BUS01 Bus Line Connector is equipped with a selector to
prevent erroneous connection of Blocks with different output voltage
specifications. Slide the selector to the output voltage for parallel
operation.
Note: Parallel operation is enabled by using a current balance
Not Using Parallel Operation
Use the S8T-BUS02 (DC line not connected). (See Figure 2.)
Figure 1:
S8T-BUS02
BUS02
L
N
L
function. For the current balance function to operate, the S8T-
BUS01 must be used.
N
−V+V
PE
DC line connected
(parallel connection)
25 W
2 blocks
5 V
120 W
S8T-BUS01
L
−V+V
N
PE
AC input
24V
12V
120 W
24 V
AC Line
DC Line
3 blocks
30 W
12 V
180 W
25 W
Figure 2:
5 V
Selector
L
N
−V+V
DC line not connected
(isolated connection)
PE
4 blocks
240 W
S8T-BUS02
L
−V+V
N
S8TS
PE
6