H3YN-41-AC100-120 Omron Automation, H3YN-41-AC100-120 Datasheet - Page 2

no-image

H3YN-41-AC100-120

Manufacturer Part Number
H3YN-41-AC100-120
Description
Relay; SSR; Timing; Multi-Function; 4PDT; Cur-Rtg 3A; Ctrl-V 100-120AC; Vol-Rtg 250AC
Manufacturer
Omron Automation
Datasheet

Specifications of H3YN-41-AC100-120

Contact Form
4PDT
Current, Rating
3 A
Display Type
LED
Function
Timing
Mounting Type
Panel
Relay Type
Solid State
Standards
UL, CSA
Temperature, Operating, Maximum
50 °C
Temperature, Operating, Minimum
-10 °C
Termination
Plug-In
Timer Type
Multi-Function
Timing Range
0.1 min. to 10 hrs.
Voltage, Control
120 VAC
Voltage, Rating
250 VAC
Timing Functions
ON-Delay, Interval, Repeat Cycle (ON-Start or OFF-Start)
Supply Voltage
100-120 VAC, 200-230 VAC, 24 VAC or 24 VDC
Control Output
DPDT, 5 A @ 250 VAC (H3YN-2); 4-DDT, 5 A @ 250 VAC (H3YN-4)
Time Range
0.1 Sec. to 10 Min. (H3YN-_ ) or 0.1 Min. to 10 Hrs. (H3YN-_ 1)
Lead Free Status / Rohs Status
RoHS Compliant part
Hold-down Clips
Specifications
■ Ratings
Note: 1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Times for details.
Y92H-3
Y92H-4
Time ranges
Rated supply voltage (See note 5.)
Pin type
Operating mode
Operating voltage range
Reset voltage
Power consumption
Control outputs
2. Single-phase, full-wave-rectified power supplies can be used.
3. When using the H3YN continuously in any place where the ambient temperature is in a range of 45°C to 50°C, supply 90% to 110% of
4. Set the reset voltage as follows to ensure proper resetting.
5. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
the rated supply voltages (supply 95% to 110% with 12 VDC type).
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
Model
Item
PYF08A, PYF08A-N, PYF08A-E
PYF14A, PYF14A-N, PYF14A-E
PY08, PY08QN(2), PY08-02
PY14, PY14QN(2), PY14-02
Applicable Socket
0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
24, 100 to 120, 200 to 230 VAC (50/60 Hz) (See note 1.)
12, 24, 48, 100 to 110, 125 VDC (See note 2.)
Plug-in
ON-delay, interval, flicker OFF start, or flicker ON start (selectable with DIP switch)
85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(See note 3.)
10% min. of rated supply voltage (See note 4.)
100 to 120 VAC: Relay ON: approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
200 to 230 VAC: Relay ON: approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
24 VAC:
12 VDC:
24 VDC:
48 VDC:
100 to 110 VDC: Relay ON: approx. 1.6 W at 110 VDC
125 VDC:
DPDT: 5 A at 250 VAC, resistive load (cosφ = 1)
4PDT: 3 A at 250 VAC, resistive load (cosφ = 1)
H3YN-2/-4/-4-Z
Relay OFF: approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
Relay OFF: approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
Relay ON: approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
Relay ON: approx. 1.1 W at 12 VDC
Relay OFF: approx. 0.1 W at 12 VDC
Relay ON: approx. 1.1 W at 24 VDC
Relay OFF: approx. 0.1 W at 24 VDC
Relay ON: approx. 1.2 W at 48 VDC
Relay OFF: approx. 0.3 W at 48 VDC
Relay OFF: approx. 0.4 W at 110 VDC
Relay ON: approx. 1.6 W at 125 VDC
Relay OFF: approx. 0.4 W at 125 VDC
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max.
selectable)
H3YN-21/-41/-41-Z
H3YN

Related parts for H3YN-41-AC100-120