Specifications of TCM320C

Frequency
315MHz
Data Rate - Maximum
125kbps
Modulation Or Protocol
ASK
Applications
General Purpose
Power - Output
5dBm
Sensitivity
-98dBm
Voltage - Supply
2.6 V ~ 3.3 V
Current - Receiving
33mA
Current - Transmitting
24mA
Data Interface
PCB, Through Hole
Memory Size
32kB Flash, 2kB RAM
Antenna Connector
On-Board, Wire Whip
Operating Temperature
-25°C ~ 85°C
Package / Case
Module
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
1084-1000
S3033-K320
USER MANUAL
TCM 300 / 300C / 320 / 320C
2.8
Modes 1 to 4 support teach-in of transmitters.
2.8.1 Setting the receiver to learning mode
2.8.2 Confirmation of Learning Mode
2.8.3 Teaching in a transmitter
In learning mode LRN, the sensitivity of the module is limited to in-room operations and
learning of repeater powered signals is disabled (to avoid unintentional learning). Therefore
ensure that the associated radio transmitter will be in a distance less than 5 m to the re-
ceiver (not necessary within Remote Learn Mode).
Trigger the telegram of the associated radio transmitter within 30 seconds:
© 2010 EnOcean | www.enocean.com
Mode
Via CLR Pin (ADIO4): Contact to GND longer than t = 2 seconds. Learning Mode LRN
is entered after clearing ID memory.
Via LRN Pin (ADIO3): Contact to GND longer than t = 0.5 seconds. In multi-channel
receiver mode, the pin has to be contacted several times until the desired channel num-
ber is selected (the number of channels is given by the selected operating mode).
Via Remote Config Control: Please refer to documentation of remote management.
Operate the switch radio transmitter (RPS or HRC) at least once (press I-button or O-
button of the rocker that is to be assigned to the selected receiver channel). If the same
rocker is operated again within 4 seconds it will still be learned. If the same rocker is op-
erated again after more than 4 seconds it will be deleted again. Please note that teach-in
without rocker information is not possible” Please note that scene switches (HRC and last
3 ID bits 0B111) cannot be teach-in!
Or activate the sensor radio transmitter (1BS, 4BS) least once with active LRN bit
(DI_3=0, please refer to “Standardization EnOcean Communication Profiles”). If the
same transmitter is operated again after more than 4 seconds with active LRN bit it will
be deleted again.
0
1
2
3
4
5
Please make sure not to remove supply voltage while in LRN mode! The flash con-
tent could get corrupted!
Confirmation
Teach-in procedure
No Learn capability
LMI HIGH continuously, LRN_TOGGLE toggling every 1 s.
LMI HIGH continuously, CHANNEL0 toggling every 1 s.
LMI HIGH continuously, current CHANNELx toggling every 1 s.
LMI HIGH continuously, DIM IND HIGH, and PWM toggling every 1 s between
10% and 100%
Reserved for future use
V1.25