774-314 PNOZ/X3/110V24V PILZ, 774-314 PNOZ/X3/110V24V Datasheet

68C6525

774-314 PNOZ/X3/110V24V

Manufacturer Part Number
774-314 PNOZ/X3/110V24V
Description
68C6525
Manufacturer
PILZ
Datasheet

Specifications of 774-314 PNOZ/X3/110V24V

Coil Voltage Vac Nom
110V
Coil Voltage Vdc Nom
24V
Contact Current Max
8A
Contact Voltage Ac Nom
240V
Contact Voltage Dc Nom
24V
Contact Configuration
3PST-NO / SPST-NC
No. Of Poles
4
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X3
Emergency stop relay and safety
gate monitor in accordance with
VDE 0113, 11/98, EN 60204-1, 12/97
and IEC 204-1, 11/98, safety
component in accordance with the
Lift Directive 95/16/EC and EN 81-1/
1998
Approvals
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland
Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Features
G Monitored manual or automatic
G 1 semiconductor output (K1/K2)
G Each AC unit can be operated
G Safety gate function with
G Only dual-channel operation will
N/C-N/O combination
reset can be selected
with 24 VDC
detect shorts across the input
contacts
PNOZ X3
G
G
G
G
Description
G 45 mm, P-93 housing, DIN-Rail
G Positive-guided relay outputs:
G Connections for
G Semiconductor output signals
G LEDs for channel 1, channel 2 and
G Increase in the number of
Technical Details
Electrical Data
Supply Voltage
Tolerance
Power Consumption
Voltage and Current at the Input and
Reset Circuits and Feedback Control Loop
Switching Capability in accordance with
EN 60947-4-1, 10/91
EN 60947-5-1, 10/91
(DC13: 6 cycles/min.)
Output Contacts
Contact Fuse Protection
(EN 60947-5-1, 10/91)
Semiconductor Outputs
External Supply Voltage
Times
Delay-on Energisation
Delay-on De-energisation
Recovery Time
Simultaneity channel 1/2
Max. Supply Interruption before De-energisation
Environmental Data
Ambient Temperature
Mechanical Data
Maximum Cross Section of
External Conductors
Dimensions (H x W x D)
Weight
mounting
– 3 safety contacts (N/O)
– 1 auxiliary contact (N/C)
– E-STOP button
– safety gate limit switch
– reset button
ready for operation
power
safety contacts available by
connecting expander modules.
2 x 1.5 mm
PNOZ X3
AC: 24, 42, 48, 110, 115, 120, 230, 240 V
DC: 24 V
85 ... 110 %
Approx.2.5 W/5 VA
24 VDC, 35 mA
AC1: 240 V/8 A/2000 VA
DC1: 24 V/8 A/200 W
AC15: 230 V/5 A; DC13: 24 V/6A
3 safety contacts (N/O),
1 auxiliary contact (N/C)
10 A quick or 6 A slow
24 VDC/20 mA, short-circuit protected
24 VDC ±20 %
Monitored manual reset: max. 100 ms
Auto./ manual reset: max. 0.3 s
With E-STOP: max. 80 ms
With power failure: max. 1 s
Approx. 1 s
¥
Approx. 25 ms
-25 ... +55 °C
Single-core or multi-core
with crimp connectors
87 x 45 x 121 mm
420 g
Operating Modes
G Single-channel operation
G Dual-channel operation
G Automatic reset
G Monitored manual reset
2
or 1 x 2.5 mm
NSG-D-2-036-07/00
2
1-1
1

Related parts for 774-314 PNOZ/X3/110V24V

774-314 PNOZ/X3/110V24V Summary of contents

Page 1

... Approvals PNOZ Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de Technical Details Electrical Data Supply Voltage Tolerance Power Consumption Voltage and Current at the Input and Reset Circuits and Feedback Control Loop ...

Page 2

... S11 S31 S21 S33 S1 S3 S12 S32 S22 S34 Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de Safety Reset circuit Input circuit contacts S33 S34 S14 S13 S11 S12 ...

Page 3

... Ooperation with automatic reset. 1L1 K6 K5 S13 S14 1L2 – Operation with monitored manual reset. 1L1 S33 S34 1L2 Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de 1 NSG-D-2-036-07/00 1-3 ...

Page 4

... DIN IEC 60068-2-3, 12/86 DIN VDE 0110 part 1, 04/97 -10 ... +55 °C -40 ... +85 °C 0.6 Nm (screws) Any Thermoplast Noryl SE 100 Mounting Housing Terminal Range Order No. 774 310 774 311 774 312 774 314 774 315 774 316 774 318 774 319 NSG-D-2-036-07/00 ...