MB1320 DENSEI-LAMBDA, MB1320 Datasheet

no-image

MB1320

Manufacturer Part Number
MB1320
Description
Three Phase Input Noise Filter with Block Terminal
Manufacturer
DENSEI-LAMBDA
Datasheet
MB13
(Note1): Value for Ta
(Note2): Calculated based on the part stress analysis prediction method as specified in MIL-HDBK-217F.
Note: For inverter application
Do not use MB series between
inverter and motor.
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
DERATING
APPLICATIONS
Specifications
Star connection
3 Phase 4 Wires 400V line-line. Unused Neutral line
ITEMS
Rated Voltage (AC)
Rated Current (AC) (Note 1)
Test Voltage
Isolation Resistance
Leakage Current
DC Resistance
Temperature Rise
Operating Temperature
Operating Humidity
Storage Temperature
Storage Humidity
Vibration
Safety Standard
Weight (typ)
MTBF(hours) (Note 2)
< =
-SERIES
MODEL
50°C. For Ta>50°C derate according to the derating curve shown below.
250V 60Hz
500V 60Hz
noise
filter
80m Ω max.
MB1310
573,000
1800g
10A
10~55~10Hz,Amplitude (Sweep for 1min) 1.5mm(9G max.) X,Y,Z 2 hours each
Three Phase Input Noise Filter with Block Terminal
2500VAC(20mA) Terminal to case, 1min. at 25˚C , 70%RH
noise
filter
100MΩ min. Terminal to case, 500VDC at 25˚C, 70%RH
30m Ω max.
Bilt to meet : UL1283,CSA C22.2 No.8, EN133200
MB1320
480,000
1800g
20A
Inverter
Delta Connection
CIRCUIT
3 Phase 3 Wires 200V line - line
30%~95% RH (No Dewdrop)
10%~95% RH (No Dewdrop)
noise
noise
filter
filter
500V(50/60Hz)
–25˚C~+85˚C
–40˚C~+85˚C
20m Ω max.
1.0mA max.
2.0mA max.
35˚C max.
MB1330
521,000
1800g
(1)Block Terminal with Cover
(2)Three Phase Power Line Filter
(3)High Attenuation in Compact Package
30A
Simple wire connection by block terminal.
High safety by terminal cover.
Available for Star connection : 400Vac line-line
Available for Delta connection : 200Vac line-line
Features
Safety standard
UL1283,
CSA Std. C22. 2 No. 8
EN133200 (New European Standard)
motor
noise
filter
11m Ω max.
MB1340
421,000
2800g
40A
7m Ω max.
MB1350
395,000
2800g
50A
141

Related parts for MB1320

MB1320 Summary of contents

Page 1

... Do not use MB series between inverter and motor. Three Phase Input Noise Filter with Block Terminal (1)Block Terminal with Cover (2)Three Phase Power Line Filter (3)High Attenuation in Compact Package MB1320 MB1330 500V(50/60Hz) 10A 20A 30A 2500VAC(20mA) Terminal to case, 1min. at 25˚C , 70%RH 100MΩ ...

Page 2

... MB13 -SERIES MB1310 MB1320 MB1330 Mounting Holes MB1340 MB1350 Mounting Holes 142 Model Name Mounting Holes Model Name (Unit: mm) ...

Page 3

... MB13 -SERIES CHARACTERISTICS Typical Insertion Loss (1) Asymmetrical MB1310 Frequency (MHz) MB1330 Frequency (MHz) MB1350 Frequency (MHz) MB1320 Frequency (MHz) MB1340 Frequency (MHz) 143 ...

Page 4

... MB13 -SERIES CHARACTERISTICS Typical Insertion Loss (2) Symmetrical MB1310 Frequency (MHz) MB1330 Frequency (MHz) MB1350 Frequency (MHz) 144 MB1320 Frequency (MHz) MB1340 Frequency (MHz) ...

Related keywords