NICFP-2020 NI [National Instruments Corporation], NICFP-2020 Datasheet

no-image

NICFP-2020

Manufacturer Part Number
NICFP-2020
Description
Relay Modules for Compact FieldPoint
Manufacturer
NI [National Instruments Corporation]
Datasheet
Overview
The National Instruments cFP-RLY-42x devices are versatile relay
modules for Compact FieldPoint that can be used to control digital
signals ranging from low voltage to 120 VDC and to 250 VAC. These
modules are commonly used to control indicator lights, motors, and
power circuits. All the modules include onboard diagnostics to ensure
trouble-free installation and maintenance. Similar relay modules are
available for FieldPoint, see page 572 for more information.
Relay Modules
NI cFP-RLY-42x modules provide built-in module-to-module
isolation to protect your Compact FieldPoint system and controller
from high voltage levels.
electrically isolated output relays so that each relay output has a
separate ground plane and each channel can be used with a different
voltage potential. Thus, you can connect one channel to a 24 VDC
and another channel on the same module to a 250 VAC.
output state of each channel. The modules all feature a maximum
switching frequency of 10 Hz (20 operations). Overall data throughput
depends on software loop speeds and network speeds.
Module
cFP-RLY-421
cFP-RLY-423
All the channels on the relay modules feature LEDs that indicates the
NI cFP-RLY-421, NI cFP-RLY-423
• 4 or 8 electromechanical relays
• Switch 250 VAC, 120 VDC
• Switch 1.5 A, maximum
• 2,300 V
• Hot swappable with autoconfiguration
• -40 to 55 °C operating range
• -40 to 60 °C operating range
overvoltage protection
(cFP-RLY-421)
(cFP-RLY-423)
8 form A (SPST), RLY-421
4 form C (SPDT), RLY-423
Output Channels
rms
bank isolation for transient
8
4
120 VDC, 250 VAC
120 VDC, 250 VAC
Output Types
Maximum
Each channel on the RLY-42x uses
Relay Modules for Compact FieldPoint
Output Current Rating
(See Specifications)
1.5 A
1.5 A
Separate Ground
per Channel
Plane
Isolation
The cFP-RLY-42x modules feature optical bank isolation with
2,300 V
double insulation for up to 250 V
FieldPoint can safely be used in applications where hazardous voltages
are present with the cFP-CB-1 connector block. These Compact
FieldPoint modules do not have channel-to-channel isolation.
Power Requirements
Because the cFP-RLY-42x are high power consumption modules,
they could limit the number of I/O modules that you can connect to
a single network interface module. Controllers and network interface
modules supply up to 9 W to power I/O modules. The RLY-421
requires up to 2.5 W and the RLY-423 requires up to 1.5 W.
Field I/O Connections
1. Relay common terminal (IC)
2. Normally open terminal (NO)
1. Normally open terminal (NO)
2. Normally closed terminal (NC)
3. Relay common terminal (IC)
Each input channel on the cFP-RLY-421 has two terminals:
Each channel of the cFP-RLY-423 has three terminals:
rms
of breakdown isolation. In addition, the modules provide
rms
NEW
of operational isolation. Compact

Related parts for NICFP-2020

NICFP-2020 Summary of contents

Page 1

Relay Modules for Compact FieldPoint NI cFP-RLY-421, NI cFP-RLY-423 • electromechanical relays • 8 form A (SPST), RLY-421 • 4 form C (SPDT), RLY-423 • Switch 250 VAC, 120 VDC • Switch 1.5 A, maximum • 2,300 ...

Page 2

Relay Modules for Compact FieldPoint SUP NO Sourcing Load IC COM To next channel cFP-RLY-421 Load + IC – Load V SUP COM cFP-RLY-423 Figure 1. Wiring Schematics for RLY Modules Specifications ...

Page 3

NI has the services and support to meet your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance – and tailored for customer requirements in research, design, validation, and ...

Related keywords