H3CA-8-AC100/110/120 Omron, H3CA-8-AC100/110/120 Datasheet - Page 9

RELAY DIGITAL DP 100/110/120VAC

H3CA-8-AC100/110/120

Manufacturer Part Number
H3CA-8-AC100/110/120
Description
RELAY DIGITAL DP 100/110/120VAC
Manufacturer
Omron
Series
H3CAr
Datasheet

Specifications of H3CA-8-AC100/110/120

Timing Range
0.1 s to 9990 Hrs
Supply Voltage
100 V to 120 V
Display Type
LCD Backlight
Termination Style
Plug, Octal Style
Contact Configuration
DPDT
Nom Input Voltage
120VAC
Delay Time Range
0.1s To 9990h
Timing Adjustment
Thumbwheel Switch
Relay Mounting
DIN Rail
No. Of Poles
2
Supply Voltage Max
120VAC
Time Range
0.1 Sec. To 9990 Hr.
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CA8AC100110120
Z2377

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
H3CA-8-AC100/110/120
Manufacturer:
Omron Electronics Inc-IA Div
Quantity:
135
Mounting Track (Meets DIN EN50022)
Protective Cover
PFP-100N/PFP-50N
Note: This dimension applied to PFP-50N.
PFP-M
Y92F-30
Y92A-48B/Y92A-48D
End Plate
Note: Pay attention to the orientation of the adapter when mounting
The protective cover protects the front panel, particularly the
time setting section, against dust, dirt and water drip, as well
as prevents the set value from being altered due to accidental
contact with the time setting knob.
Adapter for Flush Mounting
two or more timers in a vertical or horizontal line.
Y92A-48B
Hard Plastic Cover
(see note)
Y92A-48D
Soft PVC Cover
Note: The Y92A-48B Protective Cover is made of a hard plastic and
PFP-100N2
PFP-S
Note: A total of 12-25 × 4.5 elliptic holes are provided with 6 holes
therefore, must be removed to change the timer set value. However,
since the Y92A-48D Protective Cover is made of PVC, the set value
can be altered by pressing on the surface of the cover.
It may be, however, difficult to make setting changes of the Timer
with the Y92A-48B Protective Cover attached, which must be taken
into consideration before using the Y92A-48B Protective Cover.
When attaching the Y92A-48A to the Timer to be panel-mounted,
use the Y92F-30 Mounting Adapter along with the Timer.
The Protective Cover cannot be, however, used for the H3CA-FA
Series.
cut from each rail end at a pitch of 10 mm between holes.
Twelve, 25 × 4.5 elliptic holes (see note)
H3CA
9

Related parts for H3CA-8-AC100/110/120