TB1-81143 Acme Electric/Amveco/Actown, TB1-81143 Datasheet - Page 5

TRANSFORMER 100VA 120/240V

TB1-81143

Manufacturer Part Number
TB1-81143
Description
TRANSFORMER 100VA 120/240V
Manufacturer
Acme Electric/Amveco/Actown
Series
TBr
Type
Standardr
Datasheet

Specifications of TB1-81143

Maximum Power
100 VA
Primary Winding(s)
Dual
Secondary Winding(s)
Dual, No Center Tap
Series Output Voltage @ Current
24 VAC @ 4.17A
Parallel Output Voltage @ Current
12 VAC @ 8.34A
Mounting Type
Chassis Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SECTION
TA Series Secondary Fuse Kits
Type PL-112600, 601, 602: Use Dual Element Slow-Blow Fuse
TA Series Instructions for Secondary Fuse Kit
Type PL-112603: use dual element slow-blow fuse 13/32" x 1-1/2" (1.0 x 3.8 cm)
Jumper Link Connections
Group A Series: 240 V parallel: 120 V
Group B Series: 480 V parallel: 240 V
Group F series: 230 V parallel: 115 V
Group I Series: 24 V parallel: 12 V
Group J Series: 480 V & 240 V: 240 V & 120 V
Group K Series: 240 V: 120 V
Exception: 150 VA transformer TA-2-32404 does not have
quick connect terminals.
1. To attach secondary fuse kit PL-112603 to primary fuse
2. Install the fuse kits as instructed under the primary fuse kit
3. Select the appropriate pair of jumpers for making the
4. Connect the female quick-connect of the jumpers
5. Connect the ring terminal of the jumpers supplied
6. Connect secondary load lines to terminals
Mount secondary fuse clips on terminals
X1 and F or F1 using the screws supplied
with the transformer.
Connect secondary load lines to terminals
X2 and F or F2.
Use dual-element slow-blowing fuses
such as Bussmann MFG., Fusetron Type
FNM, Littelfuse or Shawmut (not supplied
with fuse kits).
kits PL-112700 thru PL-112707 snap the secondary single
pole fuse block onto the unlabeled side of the primary
double pole fuse block. (See Figure 1)
instructions on page 75.
connections between the secondary fuse block and the
secondary (X-side) of the transformer.
supplied to one of the male quick-connects of the
secondary fuse block - one jumper to each end of
the fuse block. (See Figure 2)
to screw terminals X1 and F or F1 on the secondary
(X-side) of the transformer.
X2 and F or F2.
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION
TA SERIES OPEN CORE & COIL INDUSTRIAL CONTROL TRANSFORMERS
PL-112600/601 Fuse Kit
Figure 1
LUMBERTON, NC
Connection
Series
800-334-5214
www.acmepowerdist.com
PL-112602 Fuse Kit
Connection
Parallel
Figure 2
59

Related parts for TB1-81143