3G3JX-A2004 Omron, 3G3JX-A2004 Datasheet - Page 51

AC Motor Drive

3G3JX-A2004

Manufacturer Part Number
3G3JX-A2004
Description
AC Motor Drive
Manufacturer
Omron
Datasheet

Specifications of 3G3JX-A2004

Supply Voltage Range
200V To 240V
No. Of Phases
Three
Power Rating
400W
Output Voltage Max
240V
Output Frequency Max
400Hz
Mounting Type
DIN Rail
Output Voltage Min
200V
External Height
155mm
Frequency Range
0.5 To 400Hz
Rohs Compliant
Yes
External Depth
109.5mm
External Width
80mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
• Calculating the Combined Torque and Effective Torque
*
●Selecting the Motor
Use the results of the calculations above and the equations
below to determine the required motor capacity from the effective
torque and maximum torque. Use the larger of the following
motor capacities when selecting the motor.
When selecting the motor, set a motor capacity higher than the
calculated capacity to provide some extra capacity.
• Motor Capacity Supplied for Effective Torque:
• Motor Capacity Supplied for Maximum Torque:
Effective torque: T
Maximum torque: T
Motor capacity (kW): 1.048
(N: Max. speed in r/min)
Motor capacity (kW): 1.048
(N: Max. speed in r/min)
=
Use the Servomotor's Motor Selection Software to calculate the motor
conversion inertia, effective torque, and maximum torque shown above.
Speed
(r/min)
(N m)
(N m)
0
0
Σ(Ti)
Σti
T
t
1
1
2
ti
RMS
1 cycle
MAX
N
T
T
T
(N m)
t
=
A
L
2
2
= T
1
= T
T
t
T
3
3
1
2
A
+ T
t
1
t
4
+ T
L
N
N
t
1
2
2
+ t
T
T
t
RMS
RMS
2
2
+ T
+ t
Time (s)
Time (s)
Time (s)
Time (s)
3
10
10
3
2
+ t
t
−4
−4
3
4
+ T
/1.5
4
2
t
4
Selecting the Inverter Capacity
Select an Inverter that is large enough to handle the motor
selected in Selecting the Motor above. Basically, select an
Inverter with a maximum motor capacity that matches the motor
capacity calculated above.
After selecting the Inverter, verify that the following conditions
are satisfied. If the conditions are not satisfied, select the Inverter
that is one size larger and check the conditions again.
• Motor’s rated current ≤ Inverter’s rated output current
• The application’s continuous maximum torque output time ≤
Note 1. If the Inverter's overload endurance is 120% of the rated output current
1 minute
2. Use an Inverter that is one size larger than determined by the condi-
for one minute, check for 0.8 minute.
tions above if open-loop vector control with PG is being used and a
holding torque is required at 0 r/min or a torque that is 150% or more of
the rated torque is required regularly at low frequencies (10 Hz or less).
Overview of Inverter Selection
Overview of Inverter Selection
59