GT3F-2AD24 IDEC, GT3F-2AD24 Datasheet - Page 23

Electromechanical General Purpose Timer

GT3F-2AD24

Manufacturer Part Number
GT3F-2AD24
Description
Electromechanical General Purpose Timer
Manufacturer
IDEC
Type
Off Delayr
Datasheet

Specifications of GT3F-2AD24

Leaded Process Compatible
No
No. Of Pins
8
Peak Reflow Compatible (260 C)
No
Switch Function
DPDT
Supply Voltage
250VAC
Time Range Min
0.05s
Supply Current
5A
Time Range Max
600s
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
G
GT3F Series
G-36
Operation
Time Range
Rated Voltage
Contact Rating
Contact Form
Minimum Power
Application Time
Voltage Tolerance
Repeat Error
Voltage Error
Temperature Error
Setting Error
Insulation Resistance
Dielectric Strength
Power Consumption
Mechanical Life
Electrical Life
Vibration Resistance
Shock Resistance
Operating Temperature
Storage Temperature
Operating Humidity
Weight (approximate)
1. An inrush current flows during the minimum power application time. AF20: approximate 0.3A, AD24:
2. GT3F does not read the preset time range shown on the knob after power is turned off. Note that minimizing
approximate 0.6A
the preset time, by turning the knob to zero, does not shorten the delay time after power is removed.
www.idec.com
True power OFF-delay
100 to 240V AC, 50/60Hz
24V AC/DC
250V AC/30V DC, 5A
(resistive load)
SPDT
AF20: 100 to 240V AC
AD24: 21.6 to 26.4VDC, 20.4 to 26.4VAC
100M minimum
Between power and output terminals:
2,000V AC, 1 minute (SPDT)
1,500V AC, 1 minute (DPDT)
Between contacts on different poles:
1,000V AC, 1 minute (DPDT)
Between contacts of the same pole:
750V AC, 1 minute
AF20: 3.7VA (200V AC, 60Hz)
AD24: 0.8W (DC), 1.2VA (AC)
20,000,000 operations minimum
100,000 operations minimum
100m/sec
Operating extremes:
100 m/sec
Damage limits: 500 m/sec
–10 to +50°C
–30 to +80°C
45 to 85% RH
0.05 seconds to 600 seconds
1 second
77g
UL, c-uL Listed
File No. E55996
0.2%, 10 msec
0.2%, 10 msec
0.2%, 10 msec
10% maximum
GT3F-1
2
2
(approximate 10G)
(approximate 10G)
Key features of the GT3F series include:
• Mountable in sockets or flush panel
• “True” power OFF-delay up to 10 minutes
• No external control switch necessary
• Available with reset inputs
GT3F Series — True OFF Delay Timers
2
(resistive load)
DPDT
79g
(approximate 50G)
250V AC/30V DC, 3A
GT3F-2
USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
Specifications — G-36
Part Number List — G-37
Timing Diagrams/Schematics — G-37
Instructions: Setting Timer — G-39
Instructions: Wiring Inputs — G-40
GT3 Accessories — G-48
GT3 Instructions — G-50
GT3 Dimensions — G-52
Timing Diagrams Overview — G-4
Timers
GT3F Table of Contents

Related parts for GT3F-2AD24