PAXCK010 Red Lion Controls, PAXCK010 Datasheet - Page 3

Digital Multifunction Timer

PAXCK010

Manufacturer Part Number
PAXCK010
Description
Digital Multifunction Timer
Manufacturer
Red Lion Controls
Datasheet

Specifications of PAXCK010

Time Range
0.001sec To 1hr
Power Consumption
14W
Supply Voltage Dc, Min
11V
Signal Input Type
Pulse
Supply Voltage
24VAC
Supply Voltage Max
36VDC
Time Range Max
999999h
Character Size
0.56"
Display Font Color
Red
No. Of Digits / Alpha
6
Supply Voltage Dc, Max
36V
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
1.
2. POWER:
3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected.
4. ANNUNCIATORS:
5. KEYPAD: 3 programmable function keys, 5 keys total.
6. TIMER DISPLAY:
7. CYCLE COUNTER DISPLAY:
8. REAL-TIME/DATE DISPLAY (PAXCK):
9. REAL-TIME CLOCK CARD: Field replaceable plug-in card
10. TIMER INPUTS A and B:
11. USER INPUTS: Three programmable user inputs
G
TMR -
CNT -
DAT -
DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LED
AC Versions (PAXCK000, PAXTM000):
DC Versions (PAXCK010, PAXTM010):
Timer Range: 23 Selectable Ranges
Timing Accuracy: ± 0.01%
Minimum Digit Resolution: 0.001 Sec.
Maximum Least Significant Digit Resolution: 1 Hr.
Maximum Display: 999999
Counter Range: 0 to 999999
Digit Resolution: 1 cycle
Maximum Count Rate: 50 Hz
Real-Time Display: 5 display formats
Date Display: 7 display formats
Time Accuracy: ± 5 secs./Month (1 min./year) with end-user calibration
Battery: Lithium 2025 coin cell
Battery Life Expectancy: 10 yrs. typical
Synchronization Interface: Two-wire multi-drop network (RS485 hardware),
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.
Logic inputs configurable as Current Sinking (active low) or Current
Current Sinking (active low): V
Current Sourcing (active high): V
Timer Input Pulse Width: 1 msec min.
Timer Start/Stop Response Time: 1 msec max.
Filter: Software filtering provided for switch contact debounce. Filter
Logic inputs configurable as Current Sinking (active low) or Current
Current Sinking (active low): V
Current Sourcing (active high): V
Isolation To Timer Input Common: Not isolated
Response Time: 10 msec
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)
DC Power: 11 to 36 VDC, 14 W
(Derate operating temperature to 40°C if operating <15 VDC and three
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working)
Hr/Min/Sec (12 or 24 Hr. format); Hr/Min (24 Hr.); Hr/Min (12 Hr. with
Month/Day or Day/Month (numeric or 3-letter Month format);
Day of Week/Day (3-letter Day of Week format)
32 units max., operates up to 4000 ft.
Working Voltage: 50 V. Not isolated from all other commons.
Sourcing (active high) via a single plug jumper.
Continuous Input: 30 VDC.
enabled or disabled through programming.
If enabled, filter results in 50 msec start/stop response time for successive
pulses on the same input terminal.
Sourcing (active high) through a single plug jumper.
Continuous Input: 30 VDC.
ENERAL
-
Plug-in cards are installed)
or without AM/PM indication)
Month/Day/Year or Day/Month/Year (all numeric);
Timer Display
Cycle Counter Display
Real-Time Clock Date Display
Real-Time Clock Time Display
M
IL
IL
= 0.9 V max., 22KΩ pull-up to +12 VDC.
= 0.9 V max., 22KΩ pull-up to +12 VDC.
ETER
IH
IH
= 3.6 V min., 22KΩ pull-down, Max.
= 3.6 V min., 22KΩ pull-down, Max.
SP1 -
SP2 -
SP3 -
SP4 -
S
Setpoint 1 Output
Setpoint 2 Output
Setpoint 3 Output
Setpoint 4 Output
PECIFICATIONS
3
12. MEMORY: Non-volatile E
13. ENVIRONMENTAL CONDITIONS:
14. CERTIFICATIONS AND COMPLIANCE:
15. CONNECTIONS: High compression, cage-clamp terminal block
16. CONSTRUCTION: This meter is rated for NEMA 4X/IP65 outoor use.
17. WEIGHT: 10.1 oz. (286 g)
display values.
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
Shock According to IEC 68-2-27: Operational 25 g (10g relay), 11 msec in 3
Altitude: Up to 2000 meters
SAFETY
ELECTROMAGNETIC COMPATIBILITY
Note:
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Emissions to EN 50081-1
RF interference
direction for 1.5 hours, 2 g’s.
directions.
UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2
No. 61010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
IECEE CB Scheme Test Certificate # US/8843A/UL
Refer to the EMC Installation Guidelines section for more information.
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
CB Scheme Test Report # 04ME11209-20041018
IEC 61010-1, EN 61010-1: Safety requirements for electrical
IP65 Enclosure rating (face only), IEC 529
IP20 Enclosure rating (rear of unit), IEC 529
Issued by Underwriters Laboratories, Inc.
equipment for measurement, control, and laboratory use, Part 1.
2
PROM retains all programming parameters and
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 55022
Level 3; 8 Kv air
Level 3; 10 V/m
80 MHz - 1 GHz
Level 4; 2 Kv I/O
Level 3; 2 Kv power
Level 3; 10 V/rms
150 KHz - 80 MHz
Enclosure class B
Power mains class B