K33L1A Omron, K33L1A Datasheet - Page 17

OPTION BOARD, SENSOR, PS+4-20MA

K33L1A

Manufacturer Part Number
K33L1A
Description
OPTION BOARD, SENSOR, PS+4-20MA
Manufacturer
Omron
Datasheet

Specifications of K33L1A

Accessory Type
Sensor Power Supply / Output Board
Voltage Rating
12VDC
Current Rating
80mA
Svhc
No SVHC (15-Dec-2010)
For Use With
K3HB-R Rotary Pulse Indicator, K3HB-P Timer Interval Indicator
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
■ Characteristics
Display range
Measurement range
Input signals
Connectable sensors
Max. No. of display digits
Comparative output response
time
Linear output response time
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Weight
Degree of
protection
Memory protection
Applicable standards
EMC
Front panel Conforms to NEMA 4X for indoor use (equivalent to IP66)
Rear case
Terminals
Functions F1, F2: ±2 gigacounts
Functions F3
• No-voltage contact (30 Hz max. with ON/OFF pulse width of 15 ms min.)
• Voltage pulse
• Open collector
ON residual voltage: 3 V max.
OFF leakage current: 1.5 mA max.
Load current:
5 ( 19999 to 99999)
1 ms max.: Transistor output; 10 ms max.: Relay contact output
(time until the comparative output is made when there is a forced sudden change in the input signal from 15%
to 95% or 95% to 15%)
10 ms max. (time until the final analog output value is reached when there is a forced sudden change in the
input signal from 15% to 95% or 95% to 15%)
20 M min. (at 500 VDC)
2,300 VAC for 1 min between external terminals and case
100 to 240 VAC models:
24 VAC/VDC models:
Frequency: 10 to 55 Hz; Acceleration: 50 m/s
150 m/s
Approx. 300 g (Base Unit only)
IP20
IP00 + finger protection (VDE0106/100)
EEPROM (non-volatile memory)
Number of rewrites: 100,000
UL61010C-1, CSA C22.2 No. 1010.1 (evaluated by UL)
EN61010-1 (IEC61010-1): Pollution degree 2/Overvoltage category II
EN61326: 1997, A1: 1998, A2: 2001
EMI: EN61326+A1 industrial applications
Electromagnetic radiation interference
Terminal interference voltage
EMS: EN61326+A1 industrial applications
Electrostatic Discharge Immunity
Radiated Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Conducted Disturbance Immunity
Power Frequency Magnetic Immunity
Voltage Dips and Interruptions Immunity
19,999 to 99,999
(waveform with 1-ns rising edge and pulse width of 1 s/100 ns)
(waveform with 1-ns rising edge and pulse width of 1 s/100 ns)
CISPR 11 Group 1, Class A: CISPRL16-1/-2
CISPR 11 Group 1, Class A: CISPRL16-1/-2
EN61000-4-2: 4 kV (contact), 8 kV (in air)
EN61000-4-3: 10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz, 1.4 to 2 GHz)
EN61000-4-4: 2 kV (power line), 1 kV (I/O signal line)
EN61000-4-5: 1 kV with line (power line), 2 kV with ground (power line)
EN61000-4-6: 3 V (0.15 to 80 MHz)
EN61000-4-8: 30 A/m (50 Hz) continuous time
EN61000-4-11: 0.5 cycle, 0 /180 100% (rated voltage)
1,500 V at power supply terminals in normal or common mode
1,500 V at power supply terminals in normal or common mode
2
(100 m/s
: 0 to 4 gigacounts
2
F1
F2
F3
F1
F2
F3
for relay outputs) 3 times each in 3 axes, 6 directions
Mode
Mode
Must have a switching capacity of 20 mA or higher.
Must be able to properly switch load currents of 5 mA or less.
Input frequency
0 to 30 kHz
0 to 25 kHz
0 to 50 kHz
Input frequency
0 to 30 kHz
0 to 25 kHz
0 to 50 kHz
range
range
Up/Down Counting Pulse Indicator
2
, 10 sweeps of 5 min each in X, Y, and Z directions
16 s min.
20 s min.
9 s min.
16 s min.
20 s min.
9 s min.
pulse width
pulse width
ON/OFF
ON/OFF
4.5 to 30 V
ON voltage
Note: The Up/Down Counting Pulse
Meter will malfunction if a pulse
greater than the input frequency
range is input. SYSERR may
appear on the display.
OFF voltage
30 to 2 V
K3HB-C
10 k
impedance
Input