FA1-B0-16-917-32A-BG Carling Technologies, FA1-B0-16-917-32A-BG Datasheet - Page 2

CIRCUIT BREAKER, HYD-MAG, 1P, 125V, 175A

FA1-B0-16-917-32A-BG

Manufacturer Part Number
FA1-B0-16-917-32A-BG
Description
CIRCUIT BREAKER, HYD-MAG, 1P, 125V, 175A
Manufacturer
Carling Technologies
Series
Fr
Datasheet

Specifications of FA1-B0-16-917-32A-BG

No. Of Poles
1
Current Rating
175A
Interrupting Capacity
50kA
Dielectric Strength
1.96kV
Trip Time
150s
Voltage Rating Vdc
125V
Trip Time Max
150sec
Trip Time Min
22sec
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
www.carlingtech.com
Electrical
Maximum Voltage
Current Ratings
Auxiliary Switch Rating
Insulation Resistance
Dielectric Strength
Resistance, Impedance
125VDC
Standard current coils: 100, 125,
150, 175, 225, 250 amps. 300, 350,
400, 500, 600, 700 amps available
as parallel pole construction.
SPDT; 10.1 Amps @ 250VAC, 1.0
Amps @ 65VDC, 0.5 Amps @
80VDC 0.1 Amps @ 125VAC (with
gold contacts).
Minimum: 100 Megohms at 500
VDC
1960 VAC, 50/60 Hz for one minute
between all electrically isolated ter-
minals, except 2500 VAC for one
minute between alarm/aux. switch
and main terminals with contacts in
open and closed position. F-Series
circuit breakers comply with the
8mm spacing & 3750VAC 50/60 Hz
dielectric requirements from haz-
ardous voltage to operator accessi-
ble surfaces, between adjacent
poles and from main circuits to auxi-
lary circuits per Publications EN
60950 and VDE 0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
Mechanical
Endurance
Trip Free
Trip Indication
Physical
Number of Poles
Internal Circuit Config.
Available Accessories
Weight
Standard Colors
Environmental
Designed and tested in accordance with requirements of specifi-
cation MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Vibration
Moisture Resistance
Salt Spray
Thermal Shock
Operating Temperature
F-Series – General Specifications
4000 ON-OFF operations with rated
Current & Voltage & 4000 operations
with no load (8000 operations total)
@ 5 per minute. Parallel Pole con-
struction: 1000 operations with rated
Current and Voltage @ 5 per
minute.
All F-Series Circuit Breakers will trip
on overload, even when the actuator
is forcibly held in the ON position.
The operating actuator moves posi-
tively to the OFF position when an
overload causes the circuit breaker
to trip.
1 - 3 Poles Note: Ratings over 250
Amps only available with parallel
pole.
Series (with or without auxiliary
switch), Switch Only (with or without
auxiliary switch).
Factory installed: DC Current
Metering Shunt (25 mV @lr)
Varies depending on construction.
Consult factory.
Housing - Black; Actuator- Black or
White with contrasting ON-OFF leg-
end.
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Withstands 0.060" excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C, Test
Condition A. Instantaneous and
ultrashort curves tested at 90% of
rated current.
Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56
days @ +85°C, 85% RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
-40° C to +85° C
111

Related parts for FA1-B0-16-917-32A-BG