460-480 Tyco Electronics, 460-480 Datasheet - Page 118

Voltage Transformer

460-480

Manufacturer Part Number
460-480
Description
Voltage Transformer
Manufacturer
Tyco Electronics
Series
460r
Datasheet

Specifications of 460-480

Turns Ratio
4
Transformer Mounting
Chassis
Voltage Ratio
480
Primary Voltages
480V
Power Rating
150VA
Output Voltage
120V
Mounting Type
Foot Mounted
Transformer Type
Voltage
Lead Free Status / RoHS Status
na
Frequency:
60Hz
Standard Secondary Voltage:
120 Volts Line-to-neutral
Insulation Level:
600 Volts, 10kV BIL full wave
Accuracy Class: (Per Phase)
0.6 W. 1.2 x 60Hz
Thermal Rating: (Per Phase)
150VA at 30°C amb
100VA at 55°C amb
CSA 223647
Approvals
118
UL 257877
Model 3VTN460
For line-to-neutral connection
• The model 3VTN460 is an assembly of three transformers in one case.
• The primary and secondary terminals are No. 8–32 screws into 1/2” deep brass inserts and
• The core and coil assembly is encased in a thermoplastic shell and filled with resin.
• These transformers are designed for operation line-to-neutral.
• Spacing between live parts per U.L. 1558.
• Primary fuses are current limiting, 200kA interrupting capacity, incorporating a rejection
• It is desirable to use a 1.6 amp BBS type or equal fuse in the secondary to protect
• The transformer has a clear plastic terminal cover.
• Only ground N/n terminals if source is
• See page 3 of this section for a circle diagram for the estimation of the errors for other
• Approximate weight: 24 lbs.
* Fuse Ordering
Insert F after primary voltage rating for primary fuses, insert F after primary voltage
rating for primary and secondary fuses.
fitted with one lockwasher and flatwasher.
feature, typically (class CC) KTK–R type.
the transformer.
3-phase, 4-wire effectively grounded.
than rated burdens.
See page 8 in this section for a description of its use.
3VTN460–069F*
3VTN460–120F*
3VTN460–240F*
3VTN460–277F*
3VTN460–300F*
3VTN460–346F*
Primary
Fuses Only
Catalogue Numbers
3VTN460–069FF*
3VTN460–120FF*
3VTN460–240FF*
3VTN460–277FF*
3VTN460–300FF*
3VTN460–346FF*
Secondary
Fuses
Voltage
Rating
69.3:120
300:120
240:120
346:120
277:120
120:120
Primary &
Turns
Ratio
0.58:1
2.88:1
2.31:1
2.5:1
2:1
1:1
Line to Neutral
Rec. Primary
Fuse Rating
5.0
4.0
2.0
2.0
1.5
1.5

Related parts for 460-480