460-480 Tyco Electronics, 460-480 Datasheet - Page 36

Voltage Transformer

460-480

Manufacturer Part Number
460-480
Description
Voltage Transformer
Manufacturer
Tyco Electronics
Series
460r
Datasheet

Specifications of 460-480

Turns Ratio
4
Transformer Mounting
Chassis
Voltage Ratio
480
Primary Voltages
480V
Power Rating
150VA
Output Voltage
120V
Mounting Type
Foot Mounted
Transformer Type
Voltage
Lead Free Status / RoHS Status
na
Application:
Metering
Frequency:
50 – 400Hz
Insulation Level:
600 Volts, 10kV BIL full wave
• Terminals are brass studs No. 10 – 32
• Multi ratios available upon request
• Order mounting bracket kit separately
• Approximately weight: 5.5 lbs
CSA 223647
Approvals
36
with one flatwasher, lockwasher and
regular nut
UL 257877
Model 128
Window Diameter 8.25"
120 – 201
126 – 401
126 – 501
126 – 601
126 – 751
126 – 801
126 – 102
126 – 122
126 – 152
126 – 162
126 – 202
126 – 252
126 – 302
126 – 322
126 – 352
126 – 402 4000:5
126 – 502
Catalogue
Number
2000:5
3000:5
5000:5
2500:5
3200:5
3500:5
1000:5
1500:5
1600:5
Current
Ratio
1200:5
400:5
600:5
800:5
200:5
500:5
750:5
Relay
Class
4.0
7.5
10.0
15.0
20.0
25.0
40.0
50.0
50.0
60.0
75.0
90.0
95.0
100.0
125.0
140.0
B0.1 B0.2 B0.5 B0.9 B1.8
ANSI metering class at 60Hz Secondary
0.6
0.6 0.6
0.6 0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
1.2
4.8
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
4.8
4.8
2.4
2.4
1.2
1.2
winding
resistance
(0HMS @ 75˚C
0.053
0.166
0.145
0.173
0.217
0.231
0.289
0.347
0.434
0.462
0.578
0.904
0.722
0.770
0.842
0.962
1.203
@30˚C @55˚C
2.0
2.0
2.0
2.0
2.0
2.0
2.0
Continuous
thermal
rating factor
1.5
1.5
1.5
1.33
1.0
1.33
1.33
1.0
1.0
1.0
0.8
0.8
0.8
0.8
2.0
2.0
2.0
2.0
1.5
1.5
1.5
1.33
1.0
1.0
1.0
1.0
1.0