CP1HXA40DRA Omron, CP1HXA40DRA Datasheet - Page 15

no-image

CP1HXA40DRA

Manufacturer Part Number
CP1HXA40DRA
Description
40 I/O,24DI,16DO REL,4AI,2AO
Manufacturer
Omron
Datasheet

Specifications of CP1HXA40DRA

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Serial Communications Specifications
Analogue I/O Specifications (CP1H-XA CPU Units Only)
130
Interrupt inputs
Interrupt inputs counter mode
Quick-response inputs
Scheduled interrupts
High-speed counters
Pulse outputs (models with
transistor outputs only)
Built-in analog I/O terminals
Analogue control
External analogue input
Peripheral USB port
Serial port 1
Serial port 2
Analogue
Input
Section
Analogue
Output
Section
Conversion time
Isolation method
Number of analog inputs
Input signal range
Max. rated input
External input impedance 1 M min.
Resolution
Overall accuracy
A/D conversion data
Averaging
Open-circuit detection
Number of outputs
Output signal range
Allowable external output
load resistance
External output impedance 0.5 max.
Resolution
Overall accuracy
D/A conversion data
Item
Item
Item
8 inputs (Shared by the external interrupt inputs (counter mode) and the
quick-response inputs.)
8 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits
8 points (Min. input pulse width: 50 ìs max.)
1
4 inputs: Differential phases (4x), 50 kHz or
single phase (pulse plus direction, up/down, increment),
Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range comparison
Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fi xed)
2 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus direction)
2 outputs, 1 Hz to 30 kHz (CCW/CW or pulse plus direction)
PWM outputs :(Duty ratio: 0.0% to 100.0% (Unit: 0.1%))
2 outputs, 0.1 to 1 kHz (Accuracy: ±5% at 1 kHz)
4 analogue inputs and 2 analogue
outputs (Refer to separate detailed
specifi cations.)
1 (Setting range: 0 to 255)
1 input (Resolution: 1/256, Input range: 0 to 10 V)
For connecting Peripheral Device.
Host Link, No-protocol, NT Link (1: N),
Serial PLC Link (See note.),
Serial Gateway (CompoWay/F master, Modbus-RTU master),
Modbus-RTU easy master function
Host Link, No-protocol, NT Link (1: N),
Serial PLC Link (See note.),
Serial Gateway (CompoWay/F master, Modbus-RTU master),
Modbus-RTU easy master function
XA CPU Units: CP1H-XA@@@-@
4
0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V
±15 V
1/6,000 or 1/12,000 (full scale)
25 °C: ±0.3% full scale/0 to 55 °C: ±0.6% full scale
Full scale for -10 to 10 V: F448 (E890) to 0BB8 (1770) Hex
Full scale for other ranges: 0000 to 1770 (2EE0) Hex
Supported (Set for individual inputs in the PLC Setup.)
Supported (Value when disconnected: 8000 Hex)
2 outputs
0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V
1 k min.
1/6,000 or 1/12,000 (full scale)
25 °C: ±0.4% full scale/0 to 55 °C: ±0.8% full scale
Full scale for -10 to 10 V: F448 (E890) to 0BB8 (1770) hex
Full scale for other ranges: 0000 to 1770 (2EE0) hex
1 ms/point
Photocoupler isolation between analogue I/O terminals and internal circuits. No isolation between analogue I/O signals.
Function
Voltage I/O
None
X CPU Units: CP1H-X@@@-@
Conforms to USB 1.1, B-type connector
The CP1W-CIF01 RS-232C Option Board
or the CP1W-CIF11 RS-422A/485 Option Board
can be used with either port.
0 to 20 mA or 4 to 20 mA
±30 mA
Approx. 250
25°C: ±0.4% full scale/0 to 55°C: ±0.8% full scale
0 to 20 mA or 4 to 20 mA
600
max.
6 inputs (Shared by the external interrupt inputs
(counter mode) and the quick-response inputs.)
6 inputs (Response frequency: 5 kHz max. for all
interrupt inputs), 16 bits
6 points (Min. input pulse width: 50 ìs max.)
2 inputs: Differential phases (4x), 500 kHz or single
phase, 1 MHz and 2 inputs: Differential phases (4x),
50 kHz or single phase
(pulse plus direction, up/down, increment), 100 kHz
Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range com-
parison
Trapezoidal or S-curve acceleration and deceleration
(Duty ratio: 50% fi xed)
2 outputs, 1 Hz to 1 MHz
(CCW/CW or pulse plus direction)
2 outputs, 1 Hz to 100 kHz
(CCW/CW or pulse plus direction)
PWM outputs :(Duty ratio: 0.0% to 100.0%
(Unit: 0.1%))
2 outputs, 0.1 to 1 kHz (Accuracy: ±5% at 1 kHz)
Y CPU Units: CP1H-Y@@@-@
Current I/O
Interface
Programmable Controllers

Related parts for CP1HXA40DRA