10-4 Troubleshooting Errors in Duplex Connecting Cables
10-4-1 Identifying and Correcting the Cause of the Error
Troubleshooting Errors in Duplex Connecting Cables
Break is above
Break is below
these Racks.
these Racks.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Left slot
RDY
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
Note The CPU Unit’s alarm output (alarm display) does not indicate the error.
■
Error Indications for a Disconnected/Damaged Connecting Cable
Right slot
When a duplexed Connecting Cable is disconnected or damaged, the location
of the error can be identified with Auxiliary Area flags (in A270 and A271), the
CS1D I/O Control Unit LED indicators, and the CS1D I/O Interface Unit LED
indicators.
In this example, there is an error in the Connecting Cable between Rack 1,
slot 0 and Rack 2, so the corresponding flag in A270 (A27002) is turned ON.
The flag for the same slot in the following Rack (A27004) is also turned ON.
Since the error occurred in a Connecting Cable after Rack 1, the Duplex Com-
munications Cable Status Flags are OFF for the connections between Rack 1
and Rack 2 (A27101) and between Rack 2 and Rack 3 (A27102).
The CS1D I/O Control Unit and CS1D I/O Interface Unit LED indicators all
indicate errors in the side where the break occurred. The CABLE ERR L Indi-
cator is lit red in the Units above the break and the CABLE ERR R Indicator is
lit red in the Units below the break.
RDY
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
RDY
CABLE ERR R
CABLE ERR L
END RACK
Indicates that the Connecting Cables are not duplexed
between Rack 1 and Rack 2, and between Rack 2 and Rack 3.
A270 (Duplex Communications Cable
Error Flags)
= 0014
A271 (Duplex Communications Cable Status Flags)
= 0001
Error between Rack 2, slot 0 and Rack 3
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 0
Error between Rack 1, slot 0 and Rack 2
CPU Rack
(Rack 0)
Expansion
Rack
(Rack 1)
Expansion
Rack
(Rack 2)
Expansion Rack
(Rack 3)
Errors are displayed
in all Racks after the
break.
Location of break
Section 10-4
419
Related parts for CS1D-DPL02D
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
CS1D Dual IO Control Unit
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual IO Interface Unit
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual CPU Exp
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual Exp Rack
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
G6S-2GLow Signal Relay
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Compact, Low-cost, SSR Switching 5 to 20 A
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet: