Communications Specifications
Model
Type
Communications
method
Code
Modulation
Synchronization
Transmission path
format
Transmission speed
Maximum
transmission
distance
Maximum distance
between nodes
Medium
Node connection
method
Maximum number of
nodes
Applicable
Programming
Devices
Communications
functions
Number of data link
words
Data link areas
Message length
RAS functions
Error control
Note:
1. The maximum distance between nodes depends on the processing method for connectors and cables.
2. With wired models, the maximum number of nodes is 32 if Repeater Units are not used. A Repeater Unit is required when building a network with more
3. CX-Net in CX-Programmer version 3.1 or earlier can be used only in a system with a maximum of 32 nodes (node address 1 to 32). If a system is to be used
4. If duplex Controller Link Units are used, the effective maximum number of nodes will be 62 (i.e., the maximum number of nodes in standby mode (STB)).
5. CS-series PLCs do not have a Link Area, but LR000 to LR199 are automatically converted CIO 1000 to CIO 1199.
6. Only when a CS1W-CLK13/12-V1/53/52-V1 installed in a CS1D system is used in token ring mode.
than 32 nodes. If a Repeater Unit is used, be sure to use only the following Controller Link Units or Boards and set the Wired Network 62 Node Enable Bit
in the DM Parameter Area software switches at all nodes.
with a maximum of 62 nodes (node addresses 1 to 62), use CX-Net in CX-Programmer version 3.2 or higher or the CX-Integrator.
CS1W-CLK23/CLK21-V1
CJ1W-CLK23/CLK21-V1
3G8F7-CLK23-E/CLK21-EV1
Items
CS1W-CLK23
3G8F7-CLK23-E
CS1W-CLK21-V1
3G8F7-CLK21-EV1
Wired (shielded twisted-pair cable)
N:N token-bus method
Manchester code
Baseband code
Flag synchronization (conforms to HDLC frames)
Multidrop method (bus type)
The following are the maximum transmission distances depending
2 Mbits/s: 500 m
1 Mbits/s: 800 m
500 kbits/s: 1 km
Not specified. (Maximum transmission distance must be satisfied
Specified shielded twist-pair cable
Two signal wires, one shield
PLC: Connection to terminal block
Computer: Connection using special (supplied) connector
32 or 62 nodes (See note 2 and 3.)
CX-Integrator in CX-One, CX-Net in CX-Programmer (See note 3.), and Programming Console
Data links and message service
Send words per node: 4,000 words max. (CS1W-CLK@3), 1,000 words max. (All other Units)
Number of send/receive words per node:
Total number of send words per network:
PLC: Bit areas (CIO Area, Work Area, Link Area (See note 5.)), Data Memory (DM), Extended DM Area (EM)
Computer: FinsGateway event memory
2,012 bytes max. (including the header)
・Polling node backup function
・Self-diagnosis function (hardware checking at startup)
・Echoback test and broadcast test (using the FINS command)
・Watchdog timer
・Error log function
Manchester code check
CRC check (CCITT X
on the transmission speed.
for the entire system.)
16
+X
12
+X
5
+1)
20,000 words max. (CS unit Ver. 1.2 or later)
12,000 words max. (CS Pre-Ver. 1.2)
62,000 words max.
CS1W-CLK13
3G8F7-CLK13-E
CS1W-CLK12-V1
3G8F7-CLK12-EV1
Optical Ring (H-PCF cable)
N:N token-ring method (token-ring mode)
N:N token-bus method (token-bus mode)
・ Ring method (token-ring mode)
・ Daisy-chain method (token-ring mode)
2 Mbits/s
20 km
Crimp-cut: 800 m
Adhesive polishing: 1 km (See note 1.)
H-PCF cable (two-core optical cable)
Connection using special connector (full-lock
62 (See note 4.)
・Polling node backup function
・Self-diagnosis function (hardware checking at startup)
・Echoback test and broadcast test (using the FINS command)
・Watchdog timer
・Error log function
・Node bypass function
・Transmission path duplication (for ring method in token-ring mode only)
・Disconnect detection and notification (token-ring mode only)
・Node connection configuration data reading (for ring method in token-ring mode only)
・Duplex operation of Communications Units (See note 6.)
connector or half-lock connector)
Specifications
CS1W-CLK53
3G8F7-CLK53-E
CS1W-CLK52-V1
3G8F7-CLK52-EV1
Optical Ring (GI cable)
30 km
62.5/125 μm: 2 km
50/125 μm: 1 km
GI cable (two-core optical cable:
62.5/125 μm, 50/125 μm)
Connection using ST connector
8

Related parts for CS1W-CLK53