Pulse Inputs
Reset Methods
210
Circular maximum value
Decrement
Circular Counter
Note
Phase-Z Signal (Reset Input) and Software Reset
Software Reset
If an overflow occurs, the PV of the count will remain at 7FFF FFFF hex, and if
an underflow occurs, it will remain at 8000 0000 hex. In either case, counting
will stop and the PV Overflow/Underflow Flag shown below will turn ON to
indicate the underflow or overflow.
The high-speed counter PVs are refreshed during the Motion Control Mod-
ule’s I/O refresh.
When restarting the counting operation, toggle (turn OFF and then ON) the
corresponding counter’s Reset Bit. (A860.00 is the Reset Bit for high-speed
counter 1 and A861.00 is the Reset Bit for high-speed counter 2.)
The following two methods can be set to determine the timing at which the PV
of the counter is reset (i.e., set to 0):
The PV of the high-speed counter is reset on the first rising edge of the
phase-Z signal after the corresponding High-speed Counter Reset Bit (see
below) turns ON.
The PV is reset when the High-speed Counter Reset Bit turns ON. There are
separate Reset Bits for high-speed counters 1 and 2.
Reset Bit for
High-speed
Counter 1 or 2
0
(reset input)
• High-speed counter 1: A858.01
• High-speed counter 2: A859.01
• Phase-Z signal and software reset
• Software reset
Phase-Z
Increment
1 or more cycles
Underflow
Reset
80000000 hex
Linear Counter
Within 1 cycle
0
Reset by cycle.
1 or more cycles
7FFFFFFF hex
Overflow
Section 7-5
Not reset.