XWT-ID08 Omron, XWT-ID08 Datasheet - Page 102

no-image

XWT-ID08

Manufacturer Part Number
XWT-ID08
Description
SMART SLAVE EXP 8 NPN IN
Manufacturer
Omron
Datasheet

Specifications of XWT-ID08

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XWTID08
Wiring Methods
Note
Grounding a T-branch Tap or Node Connector
The ground wire can be inserted into the connector together with the commu-
nications cable’s shield wire and both locked in place with the set screw, as
shown in the following diagram.
Grounding an Unused T-branch Tap Connector
The ground wire alone can be inserted in the connector of an unused T-
branch Tap connector, as shown in the following diagram.
1. A ground of 100 Ω max. is recommended.
2. When an acceptable ground of 100 Ω max. is available, connect the com-
3. When an acceptable ground of 100 Ω max. is not available, do not connect
munications power supply’s V- and FG terminals.
the communications power supply’s V- and FG terminals. In this case, con-
necting the V- and FG terminals may introduce noise into the network.
Ground wire
Ground wire
Section 2-4
81