XWT-ID08 Omron, XWT-ID08 Datasheet - Page 40

no-image

XWT-ID08

Manufacturer Part Number
XWT-ID08
Description
SMART SLAVE EXP 8 NPN IN
Manufacturer
Omron
Datasheet

Specifications of XWT-ID08

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XWTID08
Basic Operating Procedures
Note
1. All three power supplies can be turned ON simultaneously. It is also ac-
2. Slaves may not be recognized if the communications power supply is
3. Always operate the network with the scan list enabled in the Master Unit.
ceptable to turn ON the communications and Slave power supplies or the
Slave and PLC power supplies simultaneously.
turned ON after the Slave power supply.
When the scan list is enabled, the user can check whether Slaves are par-
ticipating in the network from the PLC and verify that the DeviceNet net-
work is communicating normally.
Section 1-4
19