Wiring Precautions
Inductive Loads
External Wiring
86
Note
When an inductive load is connected to I/O, connect a surge suppressor or
diode in parallel with the load as shown below.
Use surge suppressors and diodes with the following specifications.
Observe the following precautions for I/O wiring, power supply wiring, and
power line wiring.
Resistor: 50 Ω
Capacitor: 0.47 µF
Voltage: 200 V
Surge suppressor specifications
• When multi-conductor signal cable is being used, do not combine I/O
• If wiring racks are parallel, allow at least 300 mm between the racks.
• If the I/O wiring and power cables must be placed in the same duct, they
wires and other control wires in the same cable.
must be shielded from each other using grounded steel sheet metal.
FQM1 I/O wiring
general control circuit wiring
L
FQM1 power supply and
Diode
FQM1 I/O wiring
COM
IN
Ground to 100 Ω or less
supply and general
DC input
Power lines
FQM1 power
control wiring
Relay output or
transistor output
Relay output or
triac output
Power lines
Breakdown voltage: 3 times load voltage min.
Mean rectification current: 1 A
Ground to 100 Ω or less
Low-current cables
Control cables
Control cables
Steel sheet metal
OUT
COM
OUT
COM
Diode specifications
200 mm min.
Surge suppressor
Diode
300 mm min.
300 mm min.
L
Section 3-6
+