XW2B-80J7-1A Omron, XW2B-80J7-1A Datasheet - Page 253

no-image

XW2B-80J7-1A

Manufacturer Part Number
XW2B-80J7-1A
Description
RELAY UNIT
Manufacturer
Omron
Datasheet

Specifications of XW2B-80J7-1A

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2B80J71A
Analog Outputs
7-10-6 Application Example
Outputting the Analog
Output Value Stored
in the Auxiliary Area
Outputting a Stepped
Analog Output
Outputting a Sloped
Analog Output
230
In this example, the Motion Control Module outputs the analog output value
stored in A560 from analog output 1.
Set the following System Setup settings:
In this example, the Motion Control Module outputs a step-pattern analog out-
put using a particular input signal as the trigger.
Set the following System Setup settings:
In this example, the Motion Control Module outputs a sloped analog output
using a particular input signal as the trigger.
Set the following System Setup settings:
• Analog Input/Output Tab Page − Output 1: Set the output range of analog
• Analog Input/Output Tab Page − Output: Set the analog output refreshing
• Analog Input/Output Tab Page − Output 1: Set the output range of analog
• Analog Input/Output Tab Page − Output: Set the analog output refreshing
• Analog Input/Output Tab Page − Output 1: Set the output range of analog
• Analog Input/Output Tab Page − Output: Set the analog output refreshing
0002.01
output 1 to “1 to 5 V.”
method to END refresh.
output 1 to “1 to 5 V.”
method to immediate refresh.
output 1 to “1 to 5 V.”
method to immediate refresh.
0002.01
0002.01
D00000
D00001
D00000
0
0
0
3
1
7
E
D
9
@ACC
@SPED
8
0
0
D00000
@MOV
D00000
SET
#0001
#0000
Specified analog output value = 03E8 hex
(1,000 decimal = 25%)
#0001
#0000
Rate of change: 0190 hex
(400 decimal = 10%)
Specified analog output value = 07D0 hex
(2,000 decimal = 50%)
A564.00
#1000
A560
When CIO 0002.01 goes ON, ACC is
executed to output a sloped analog
signal from analog output port 1, with an
output range of 1 to 5 V, an analog output
target value of 07D0 hex (50% = 3 V), and
slope of 0190 hex (10% = 0.4 V) every 2 ms.
When CIO 0002.01 goes ON, SPED is
executed to output a stepped analog
signal from analog output port 1, with an
output range of 1 to 5 V, and an analog
output value of 03E8 hex (25% = 2 V).
When CIO 0002.01 goes ON, MOV
stores 1000 hex in A560 (Analog
Output 1 Output Value).
Turns ON A564.00 (Analog Output 1
Conversion Enable Bit).