APL111-23486-2

Manufacturer Part Number
APL111-23486-2
Description
Circuit Breaker, Magnetic Circuit Breakers
Manufacturer
Airpax Corporation
Datasheet
140
Trip Free
Will trip open on overload, even when the handle is forcibly
held on or restrained. This prevents operator from damaging
the circuit by holding the handle in the ON position.
Trip Indication
The operating handle moves positively to the OFF position
on overload.
Ambient Operation
Operates normally in temperatures between -40°C and +85°C.
Insulation Resistance
Not less than 100 megohms at 500Vdc.
Dielectric Strength
Withstands 1500Vac at 60Hz for 60 seconds or 1800Vac for
one second from terminal to terminal, and from auxiliary
switch terminal to main terminal.
Endurance
Per UL 1077 (6000 operations at rated load plus 4000
operations with no load). Tested at a maximum rate of 6
times per minute. Rating above 50 amperes operate a
minimum of 5000 operations.
Shock
Withstands 100G or more without tripping while carrying full
rated current per MIL-Std-202, Method 213, Test Condition I.
Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and dual
coil configurations are tested at 80% of rated current. Breakers
mounted in the handle down position are to be tested with no
current applied (per MIL-PRF-55629).
Vibration
Withstands 10G without tripping while carrying full rated
current per MIL-Std-202, Method 204, Test Condition A.
Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and
dual coil configurations are tested at 80% of rated current.
Dual Coil Ratings
5-65Vdc and 5-250Vac for three terminal configurations.
5-120Vac and 5-120Vdc for four terminal configurations.
Not available in delays 64, 65 and 66.
APL/UPL Specifications
APL/UPL SPECIFICATIONS
APL Ratings
0.050-50 amperes, 65Vdc, 250Vac maximum, 50/60Hz or
400Hz. 51-100 amperes at 65Vdc and 120Vac maximum.
Ratings of 0.050-20 amperes at 277Vac, 50/60Hz are available
upon request.
Auxiliary Switch Ratings
(APL/UPL, 205/295)
REC4 and REC5 are rated at 10 amperes, 250Vac or 3 amperes,
50Vdc. REG4 and REG5 are rated at 0.1 amperes, 125Vac.
UPL Ratings
UPL breakers are UL (File No. E-66410) and CSA (File No.
LR-26229) recognized as Component Appliance Controls in
the following configurations and ratings. Consult factory for
further information.
Configurations
Series, Shunt, Relay, Auxiliary Switch, Switch Only,
Dual Coil, No Voltage.
Poles
One through nine.
Moisture Resistance
Designed to meet the requirements of MIL-PRF-55629 when
tested in accordance with Method 106 of MIL-Std-202.
Salt Spray (Corrosion)
Designed to meet the requirements of MIL-PRF-55629 when
tested in accordance with Method 101 of MIL-Std-202.
Recommended Torque Specifications
6-32 mounting inserts
M3 mounting inserts
10-32 stud terminals
M5 stud terminals
⁄/¢-28 stud terminals
Approximate Weight Per Pole
Ounces
3.7
Grams
103
6-8 inch pounds
4-5 inch pounds
13-14 inch pounds
13-14 inch pounds
25-30 inch pounds