APL111-23486-2 Airpax Corporation, APL111-23486-2 Datasheet - Page 21

no-image

APL111-23486-2

Manufacturer Part Number
APL111-23486-2
Description
Circuit Breaker, Magnetic Circuit Breakers
Manufacturer
Airpax Corporation
Datasheet
*Use 0 in place of 1 when ordering switch only.
Multi-pole units with mixed construction, poles numbered left
to right when viewed from terminal end.
*Can be used for Solder Terminals also.
APL
UPL
MPL
0*
1
11
111
1111
1
-0
-1
-1REC4
-1REC5
-1REG4
-1RS
-3
-5
2
3
First
Type
Internal Configuration
Third Decision
Second Decision
Poles
Decision
Switch only (no overload sensing)
Single pole unit
Two pole unit
Three pole unit
Four pole unit
Magnetic circuit breaker in
a molded phenolic case
UL and CSA recognized as
a component-appliance control
UL and CSA recognized as a
“manual across the line starter”
Switch only
(omit 4th and 5th decisions)
Series
Series with auxiliary switch
*.110 quick connect terminals
Series with auxiliary switch
*.187 quick connect terminals
Series with auxiliary switch
(gold contacts) *.110
quick connect terminals
Series with alarm switch
electrical trip turret terminals
Shunt
Relay
40*
41*
42*
43*
49*
50
51
52
53*
59
60
61
62
64
65
66*
69
70*
71*
72*
73*
For addition of inertial delay, add an “F” to any delay
number, except 40, 50, 60 and 70.
*Not available above 50 amperes.
4
Example:
UPL 11 - 1 - 61- 203
Fourth Decision
Hz and Delay
1
400Hz 150% instant trip
400Hz short delay
400Hz long delay
400Hz motor start
400Hz 130% instant trip
DC 150% instant trip
DC short delay
DC long delay
DC motor start
DC 125% instant trip
50/60Hz 150% instant trip
50/60Hz short delay
50/60Hz long delay
50/60Hz short delay
(high pulse)
50/60Hz long delay
(high pulse)
50/60Hz motor start (high pulse)
50/60Hz 125% instant trip
DC-50/60Hz 150% instant trip
DC-50/60Hz short delay
DC-50/60Hz long delay
DC-50/60Hz motor start delay
2
3
4
5
5
See page 15 for maximum voltage ratings.
(Note C, page 20)
Standard current ratings listed.
For other ratings, please consult the factory.
*Switch only ratings.
A
B
C
M
H
9
6
Nominal Amperage Rating
Current Code
101
251
501
751
102
252
502
752
103
153
203
303
353
403
503
603
703
803
903
104
Fifth Decision ( Note A )
Optional
Sixth Decision
Metric thread mounting inserts
and terminals (Note D)
Barrier (style C page 5)
multi-pole only
277Vac 50/60Hz
(see page 15 for details)
Fungus (note B)
International handle markings
White handle (note E)
APL/UPL Decision Tables
Ratings (Amps)
*100.0
*50.0
10.0
15.0
20.0
30.0
35.0
40.0
60.0
70.0
80.0
90.0
1.00
2.50
5.0
7.50
.100
.250
.500
.750
147