PowerFlex® 40P
TECHNICAL DATA
ADJUSTABLE FREQUENCY AC DRIVES

Related parts for 22D-B2P3N104

22D-B2P3N104 Summary of contents

Page 1

PowerFlex® 40P ADJUSTABLE FREQUENCY AC DRIVES TECHNICAL DATA ...

Page 2

Product Description As part of the industry leading PowerFlex® family of AC drives, the PowerFlex 40P addresses your needs for closed loop control and category 3 Safe-off in a compact and cost effective design. The PowerFlex 40P AC drive is ...

Page 3

PowerFlex 40P Technical Data PowerFlex 40P AC Drive Features Flexible Packaging and Mounting Options • Versatile packaging options allow for panel mount NEMA 1/IP30 as well as NEMA 4/IP66 (with like enclosure) using the plate/flange drives. • Plate drives also ...

Page 4

PowerFlex 40P PC Programming Software Through the use of a Serial Converter Module and DriveExplorer™ or DriveTools™ SP software, programming can be greatly simplified. DriveExplorer Software • View and modify drive and adapter parameters in a method similar to the ...

Page 5

PowerFlex 40P Technical Data Sensorless Vector Control • Sensorless Vector Control provides exceptional speed regulation and very high levels of torque across the entire speed range of the drive. • The Autotune feature allows the PowerFlex 40P AC drive to ...

Page 6

PowerFlex 40P Technical Data I/O • Two (2) semi-programmable digital inputs. - Dedicated for start and stop - Simplifies wiring and troubleshooting • Five (5) fully programmable digital inputs provide application versatility. - Standard 27 different settings, same as PowerFlex ...

Page 7

Communication Options • PowerFlex 40P AC drives are compatible with any device that acts as a RTU Master and supports standard 03, 06 and 16 RTU commands. • A network can be configured using PowerFlex 40P AC drives with optional ...

Page 8

PowerFlex 40P Technical Data PowerFlex 40P AC Drive Advanced Features Closed Loop Encoder/Pulse Train Input Standard The PowerFlex 40P AC drive allows for configurable closed loop control for either speed or position feedback for improved speed regulation, basic position control, ...

Page 9

... With the DriveGuard option, category 3 Safe-off combines safety and productivity with zone control and cost savings through the reduction of components. The PowerFlex 40P AC drive with the Allen-Bradley DriveGuard relay board option is a certified safety solution for AC drive control per EN954-1. Series B, 20-DG01 ...

Page 10

PowerFlex 40P Technical Data Application-Specific Features Beverage and Brewing Industry • Embedded Encoder in a compact and cost effective design - Reduction in dedicated sensors to track product position during production cycle - More process reliability and control, allowing for ...

Page 11

Automotive Industry • Embedded Encoder in a compact and cost effective design. - Sensorless Vector with encoder feedback provide increased reliability - Position Regulator: reduction in sensors required to control process - Local logic (StepLogic) for time or digital input ...

Page 12

... Catalog Number Explanation 1 6-8 22D – B 2P3 Drive Code Type 22D PowerFlex 40P b Voltage Rating Code Voltage Ph. B 240V 480V 600V Position Rating 200-240V Three-Phase Input Code Amps kW (Hp) 2P3 2.3 0.4 (0.5) 5P0 5.0 0.75 (1.0) 8P0 8 ...

Page 13

... B 4.0 5.0 6.6 B 5.5 7.5 9 ➊ Meets IP 40/54/65 (NEMA 1/12/4/4X) when installed in an enclosure of like rating. Cat. No. IP20 Plate Drive 22D-B2P3N104 22D-B2P3H204 22D-B5P0N104 22D-B5P0H204 22D-B8P0N104 22D-B8P0H204 22D-B012N104 22D-B012H204 22D-B017N104 22D-B017H204 22D-B024N104 22D-B024H204 22D-B033N104 22D-B033H204 Cat. No. IP20 Plate Drive 22D-D1P4N104 22D-D1P4H204 22D-D2P3N104 22D-D2P3H204 22D-D4P0N104 ...

Page 14

... Compatibility: Windows 98, ME, NT, 4.0 (Service Pack 3 or later), 2000 and XP. ➊➋➌ Pocket DriveExplorer™ Software “Windows” based software package for monitoring and configuring Allen-Bradley drive and communication adapters. ➊ Setup Wizards are available for use with DriveTools SP and DriveExplorer (Lite/Full) only. ...

Page 15

... If NEMA 1/IP30 is required, must also order 22-JBCB (Frame B drives) or 22-JBCC (Frame C drives). Catalog Number SK-U1-FAN1-B1 SK-U1-FAN2-B1 SK-U1-FAN1-C1 SK-U1-FAN1-C2 SK-U1-DCVR3-B1 SK-U1-DCVR3-C1 SK-U1-DCVR4-EN Catalog Number 20A-DG01 Catalog No. 1203-USB 22-SCM-232 1203-SFC 1203-SNM 22-RJ45CBL-C20 AK-U0-RJ45-SC1 AK-U0-RJ45-TR1 AK-U0-RJ45-TB2P 22-COMM-C 22-COMM-D 22-COMM-E 22-COMM-L 22-COMM-P 20-XCOMM-DC-BASE 20-XCOMM-AC-PS1 1769-SM2 22D-CCB ➊ 22D-CCC ➊ 15 ...

Page 16

PowerFlex 40P Technical Data Dynamic Brake Resistors Drive Ratings Input Voltage kW 240V 50/60 Hz 3-Phase 0.4 0.75 1.5 2.2 3.7 5.5 7.5 480V 50/60 Hz 3-Phase 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 600V 50/60 Hz 3-Phase 0.75 ...

Page 17

EMC Filters Drive Ratings Input Voltage kW 240V 50/60 Hz 3-Phase 0.4 0.75 1.5 2.2 3.7 5.5 7.5 480V 50/60 Hz 3-Phase 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 600V 50/60 Hz 3-Phase 0.75 1.5 2.2 4.0 5.5 7.5 ...

Page 18

... There are many other factors that must be considered for optimal performance in any given application. The block diagram below highlights the primary installation considerations. Consult the PowerFlex 40P User Manual, Publication … 22D-UM001 available online at http://www.rockwellautomation.com/literature, for detailed recommendations on input power conditioning, CE conformance (EMC filtering), FCC Compliance, reflected wave protection, motor cable types and motor cable distances ...

Page 19

PowerFlex 40P Technical Data Power Terminal Block Terminal Block Specifications Name Frame Power Terminal Block B C ➊ Maximum/minimum sizes that the terminal block will accept - these are not recommendations. Terminal ➋ Description ➌ R/L1, S/L2 1-Phase Input R/L1, ...

Page 20

PowerFlex 40P Technical Data Control Wiring • The control logic is 24V DC and can be set for either Sink or Source control via a DIP switch setting. • Control terminal screws are sized for a conventional blade screw driver. ...

Page 21

Control I/O Terminal Designations No. Signal Default R1 Relay N.O. Fault R2 Relay Common – R3 Relay N.C. Fault Analog Output Select 0-10V DIP Switch Sink/Source Source (SRC) DIP Switch Stop ➊ 01 Coast 02 Start/Run FWD Not Active 03 ...

Page 22

... AC – 3-Phase Input 575V 3-Phase Output 22D-E1P7 0.75 (1.0) 1.7 22D-E3P0 1.5 (2.0) 3.0 22D-E4P2 2.2 (3.0) 4.2 22D-E6P6 4.0 (5.0) 6.6 22D-E9P9 5.5 (7.5) 9.9 22D-E012 7.5 (10) 12.2 22D-E019 11 (15) 19.0 ➊ Ratings apply to all drive types; Panel Mount (N104), Flange Mount (F104), and Plate Drive (H204). ➋ Refer to the Bulletin 140M Motor Protectors Selection Guide, publication 140M-SG001… to determine the frame and breaking capacity required for your application. ...

Page 23

PowerFlex 40P Technical Data Category Specification Agency Certification The drive is also designed to meet the appropriate portions of the following specifications: NFPA National Electrical Code NEMA ICS 3.1 - Safety standards for Construction and Guide for ...

Page 24

Category Specification Control Method: Carrier Frequency Frequency Accuracy Digital Input: Analog Input: Analog Output: Speed Regulation Open Loop with Slip Compensation: With Encoder: Output Frequency: Efficiency: Stop Modes: Accel/Decel: Intermittent Overload: Electronic Motor Overload Protection Control Inputs Digital: Bandwidth: Quantity: ...

Page 25

PowerFlex 40P Technical Data Parameter List Parameter Number Parameter Name Description Basic Display Group b001 Output Freq Output frequency present at T1, T2 & T3 (U, V & W). b002 Commanded Freq Value of the active frequency command. b003 Output ...

Page 26

PowerFlex 40P Technical Data Parameter Number Parameter Name Description A062 Opto Out2 Level 0.0 to 9999 A064 Opto Out Logic A065 Analog Out Sel 21 settings; OutFreq 0-10, OutCurr 0-10, OutVolt 0-10, OutPowr 0-10, TstData 0-10, OutFreq ...

Page 27

Parameter Number Parameter Name Description A123 10V Bipolar Enbl 2 settings; Uni-Polar In, Bi-Polar In A124 Var PWM Disable 2 settings; Enable, Disable A125 Torque Perf Mode 2 settings; V/Hz, Sensrls Vect A126 Motor NP FLA 0.1 to (Drive Rated ...

Page 28

PowerFlex 40P Technical Data Parameter Number Parameter Name Description E222 Positioning Mode E223 Find Home Freq 0.1 to 500.0 Hz E224 Find Home Dir 2 settings; Forward, Reverse E225 Encoder Pos Tol 1 to 50000 E226 Counts ...

Page 29

PowerFlex 40P Technical Data Approximate Dimensions Ratings are in kW and (HP). Frame 240V AC – 3-Phase B 0.4 (0.5) 2.2 (3.0) 0.75 (1.0) 3.7 (5.0) 1.5 (2.0) C 11.0 (15.0) 18.5 (25.0) 15.0 (20.0) 22.0 (30.0) IP 30/NEMA 1/ ...

Page 30

PowerFlex 40P Technical Data IP 30/NEMA 1/UL Type 1 Option Kit with Communication Option 77.5 (3.05) 50.0 (1.97) 22.5 (0.89) ∅ 22.2 (0.87) 134.3 (5.29) 105.3 (4.15) 76.3 (3.00) 108.7 (4.28) 92.2 (3.63) 69.2 (2.72) 45.7 (1.80) 22.2 (0.87) 109.8 ...

Page 31

... RUN RUN REV REV FAULT FAULT 210 (8.27) 5.3 (0.21) 7.5 (0.30) Frame B — Flange Mount 300 (11.81) 5.3 (0.21) RUN REV FAULT 291.5 (11.48) 8 (0.31) Frame C — Flange Mount 119.3 (4.70) 94.3 63.1 (3.71) (2.48) 250 (9.84) 22D-CCB 130.3 (5.13) 105.8 138.2 (4.17) (5.44) 325 (12.8) 22D-CCC 31 ...

Page 32

... PowerFlex 40P Technical Data Plate Drive 125 (4.92) 112 (4.41) 80 (3.15) RUN RUN REV REV FAULT FAULT (3.78) 100 (3.94) 155 (6.10) 142 (5.59) 80 (3.15) RUN REV FAULT 130 (5.12) 32 113 (4.45) 88 (3.46) 192 (7.56) 204 180 (8.03) (7.09) 96 22D-CCB 5.3 (0.21) Frame B — Plate Drive 123.5 (4.86) 98.5 (3.88) 272 (10.71) 284 260 (11.18) (10.24) 136 (5.35) 5.3 22D-CCC (0.21) Frame C — Plate Drive 9.5 (0.37) 9.5 (0.37) ...

Page 33

PowerFlex 40P Technical Data EMC Line Filters Catalog Numbers: 22-RF0P8-BL; 22-RF012-BS, -BL (Series B); 22-RF021-BS, -BL Catalog Numbers: 22-RF018-CS, -CL; 22-RF025-CL; 22-RF026-CS, -CL; 22-RF034-CS, -CL (1.26) (0.67) Dimensions are in millimeters and (inches) 50 100 (1.97) (3.94) 78 29.8 (3.07) ...

Page 34

PowerFlex 40P Technical Data Human Interface Module (HIM) Dimensions NEMA Type 1 Bezel – Dimensions are in millimeters and (inches) Catalog Number: 22-HIM-B1 25.2 (0.99 (2.64) 60 (2.36) 4.8 (0.19) 77 (3.03) 19.1 (0.75) 23.5 (0.93) 34 NEMA ...

Page 35

PowerFlex 40P Technical Data Notes 35 ...

Page 36

... Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication 22D-TD001C-EN-P – May 2007 Supersedes 22D-TD001B-EN-P – August 2006 Copyright © 2007 Rockwell Automation, Inc. All rights reserved. Printed in USA. ...