22D-B2P3N104 Allen-Bradley, 22D-B2P3N104 Datasheet - Page 26

no-image

22D-B2P3N104

Manufacturer Part Number
22D-B2P3N104
Description
Powerflex 40p
Manufacturer
Allen-Bradley
Datasheet
PowerFlex 40P Technical Data
26
Parameter
Number
A062
A064
A065
A066
A067
A068
A069
A070
A071
A072
A073
A074
A075
A076
A077
A078
A079
A080
A081
A082
A083
A084
A085
A086
A087
A088
A089
A090
A091
A092
A093
A094
A095
A096
A097
A098
A099
A100
A101
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
A112
A113
A114
A115
A116
A117
A118
A119
A120
A121
A122
Parameter Name
Opto Out2 Level
Opto Out Logic
Analog Out Sel
Analog Out High
Accel Time 2
Decel Time 2
Internal Freq
Preset Freq 0
Preset Freq 1
Preset Freq 2
Preset Freq 3
Preset Freq 4
Preset Freq 5
Preset Freq 6
Preset Freq 7
Jog Frequency
Jog Accel/Decel
DC Brake Time
DC Brake Level
DB Resistor Sel
S Curve %
Boost Select
Start Boost
Break Voltage
Break Frequency
Maximum Voltage
Current Limit 1
Motor OL Select
PWM Frequency
Auto Rstrt Tries
Auto Rstrt Delay
Start At PowerUp
Reverse Disable
Flying Start En
Compensation
SW Current Trip
Process Factor
Fault Clear
Program Lock
Testpoint Sel
Comm Data Rate
Comm Node Addr
Comm Loss Action
Comm Loss Time
Comm Format
Language
Anlg Out Setpt
Anlg In 0-10V Lo
Anlg In 0-10V Hi
Anlg In4-20mA Lo
Anlg In4-20mA Hi
Slip Hertz @ FLA
Process Time Lo
Process Time Hi
Bus Reg Mode
Current Limit 2
Skip Frequency
Skip Freq Band
Stall Fault Time
Analog In Loss
Description
0.0 to 9999
0 to 3
21 settings; OutFreq 0-10, OutCurr 0-10, OutVolt 0-10, OutPowr 0-10, TstData 0-10,
OutFreq 0-20, OutCurr 0-20, OutVolt 0-20, OutPowr 0-20, TstData 0-20, OutFreq 4-20,
OutCurr 4-20, OutVolt 4-20, OutPowr 4-20, TstData 4-20, OutTorq 0-10, OutTorq 0-20,
OutTorq 4-20, Setpnt 0-10, Setpnt 0-20, Setpnt 4-20
0 to 800%
0.0 to 600.0 Secs
0.0 to 600.0 Secs
0.00 to 600.0 Hz
0.00 to 500.0 Hz
0.00 to [Maximum Freq]
0.1 to 600.0 Secs
0.0 to 99.9 Secs
0.0 to (Drive Rated Amps x 1.8)
0 to 99
0 to 100%
15 settings: Custom V/Hz; 30.0, VT (Variable Torque); 35.0, VT; 40.0, VT; 45.0, VT; 0.0 no IR;
0.0; 2.5, CT (Constant Torque); 5.0, CT; 7.5, CT; 10.0, CT; 12.5, CT; 15.0, CT;17.5, CT; 20.0,
CT
0.0 to 25.0%
0.0 to 100.0%
0.0 to 500.0 Hz
20 to Drive Rated Volts
0.1 to (Drive Rated Amps x 1.8)
3 settings; No Derate, Min Derate, Max Derate
2.0 to 16.0 kHz
0 to 9
0.0 to 120.0 Secs
2 settings; Disabled, Enabled
2 settings; Rev Enabled, Rev Disabled
2 settings; Disabled, Enabled
4 settings; Disabled, Electrical, Mechanical, Both
0.0 to (Drive Rated Amps x 2)
0.1 to 999.9
3 settings; Ready/Idle, Reset Fault, Clear Buffer
2 settings; Unlocked, Locked
400 to FFFF Hex
6 settings; 1200, 2400, 4800, 9600, 19.2K, 38.4K
1 to 247
4 settings; Fault, Coast Stop, Stop, Continu Last
0.1 to 60.0 Secs
6 settings; RTU 8-N-1, RTU 8-E-1, RTU 8-O-1, RTU 8-N-2, RTU 8-E-2, RTU 8-O-2
7 settings; English, Francais, Espanol, Italiano, Deutsch, Portugues, Nederlands
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 10.0 Hz
0.00 to 99.99
0.00 to 99.99
2 settings; Disabled, Enabled
0.1 to (Drive Rated Amps x 1.8)
0 to 500 Hz
0.0 to 30.0 Hz
6 settings; 60 Seconds, 120 Seconds, 240 Seconds, 360 Seconds, 480 Seconds, Flt Disabled
7 settings; Disabled, Fault, Stop, Zero Ref, Min Freq Ref, Max Freq Ref, Int Freq Ref
0.0
Disabled
RTU 8-N-1
0.0%
Factory Default
0
OutFreq 0-10
100%
20.0 Secs
20.0 Secs
60.00 Hz
0.00 Hz
5.00 Hz
10.00 Hz
20.00 Hz
30.00 Hz
40.00 Hz
50.00 Hz
60.00 Hz
10.00 Hz
10.0 Secs
0.0 Secs
0
0%
5.0, CT
2.5, CT: 5, 7.5, 10 & 15 Hp
2.5%
25.0%
15.0 Hz
Drive Rated Volts
Drive Rated Amps x 1.5
No Derate
4.0 kHz
0
1.0 Secs
Rev Enabled
Disabled
Electrical
0.0 (Disabled)
30.0
Ready/Idle
Unlocked
400
9600
100
Fault
5.0 Secs
English
0.0%
100.0%
0.0%
100.0%
2.0 Hz
0.00
0.00
Enabled
Drive Rated Amps x 1.5
0 Hz
0.0 Hz
60 Seconds
Disabled
Drive Rated Amps x 0.05