Analog I/O Units CS1W-MAD44
Specifications
Applicable PLC model
Unit type
Isolation
External terminals
Power consumption
Dimensions (mm) *1
Weight
General specifications
Mounting position
Maximum number of Units
Data exchange with CPU
Units
Input
Specifications
Functions
Item
CS series
CS1 Special I/O Unit
Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
21-point detachable terminal block (M3 screws)
200 mA max. at 5 VDC, 200 mA max. at 26 VDC
35 × 130 × 126 (W × H × D)
450 g max.
Conforms to general specifications for SYSMAC CS-series Series.
CS-series CPU Rack or CS-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.)
Units per Rack (CPU Rack or
Expansion Rack) *2
Units per basic system
Special I/O Unit Area
CIO 200000 to CIO 295915
(Words CIO 2000 to CIO 2959)
Internal Special I/O Unit DM Area
(D20000 to D29599)
Input signal *4
Number of analog inputs
Input signal range *3
Maximum rated input (for 1 point) *5
Input impedance
Resolution
Converted output data
Accuracy *6
A/D conversion time *7
Mean value processing
Peak value holding
Input disconnection detection *9
Power Supply Unit
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PD204
C200HW-PA209R
When C200HW-PA209R Power Supply Units only are used:
6 Units max. × 8 Racks = 48 Units max.
Exchanges 10 words of data per
Unit.
Transmits 100 words of data per
Unit at power-up or when the
Unit is restarted.
23±2°C
0°C to 55°C
Voltage input
4
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
±15 V
1 MΩ min.
4,000 (full scale)
16-bit binary data
±0.2% of full scale
±0.4% of full scale
1.0 ms/point max.
Stores the last "n" data conversions in the buffer, and stores the the mean value
of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Detects the disconnection and turns ON the Disconnection Detection Flag.
CS1W-MAD44
Maximum number of Units per Rack
3 Units max.
6 Units max.
CPU Unit to Analog
I/O Unit
Analog I/O Unit to
CPU Unit
CPU Unit to Analog
I/O Unit
Analog output
Peak value hold
Conversion Enable Bit
Analog input
Input disconnection detection
Alarm flags
Input signal conversion enable/disable,
input signal range setting
Output signal conversion enable/disable,
output signal range setting
Ratio conversion function setting,
constants
Output status for output hold
Mean value function setting
Current input
4 to 20 mA
±30 mA
250 Ω (rated value)
±0.4% of full scale
±0.6% of full scale
CS1W-AD/DA/MAD