cs1w-ad Omron Corporation, cs1w-ad Datasheet - Page 9

no-image

cs1w-ad

Manufacturer Part Number
cs1w-ad
Description
Cs Series Analog I/o Unit
Manufacturer
Omron Corporation
Datasheet
Analog Outputs Units CS1W-DA041/DA081/DA08C
Specifications
*1. Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit.
*2. Refer to Dimensions on page 20 for details on the Unit's dimensions.
*3. Maximum Number of Units
*4. Data Exchange with CPU Units
*5. Output signal ranges can be set for each output.
*6. The accuracy is given for full scale. For example, an accuracy of ±0.3% means a maximum error of ±12 (BCD).
*7. D/A conversion time is the time required for converting and outputting the PLC data. It takes at least one cycle for the data stored in the PLC
*8. When the operation mode for the CPU Unit is changed from RUN mode or MONITOR mode to PROGRAM mode, or when the power is turned
*9. The load resistance is adjusted to 250 Ω at the factory. Always adjust the offset gain before application when the load resistance is not 250 Ω.
Applicable PLC model
Unit type
Isolation *1
External terminals
Power consumption
Dimensions (mm) *2
Weight
General specifications
Mounting position
Maximum number of Units
Data exchange with CPU Units *4
Output
specifications
Output
functions
The maximum number of Units that can be mounted to one Rack varies depending on the current consumption of the other Units mounted to
the Rack and may be less than the number shown in the above table.
to be read by the Analog Output Unit.
ON, the Output Conversion Enable Bit will turn OFF. The output status specified according to the output hold function will be output.
The CS1W-DA041 is adjusted for current outputs (load resistance: 250 Ω) at the factory. Adjust the offset gain before application when using
voltage outputs.
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PD204
C200HW-PA209R
Special I/O Unit Area
CIO 200000 to CIO 295915
(Words CIO 2000 to CIO 2959)
Internal Special I/O Unit DM Area
(D20000 to D29599)
Power Supply Unit
Number of analog outputs
Output signal ranges *5
Output impedance
Max. output current
(for 1 point)
Maximum permissible load
resistance
Resolution
Set data
Accuracy *6
D/A conversion time *7
Output hold function
Item
3 Units max.
7 Units max.
CS1W-DA041/08V
Exchanges 10 words of data
per Unit.
Transmits 100 words of data
per Unit at power-up or when
the Unit is restarted.
CS series
CS1 Special I/O Unit
Between I/O and PLC signals: Photocoupler
(No isolation between individual I/O signals.)
21-point detachable terminal block (M3 screws)
130 mA max. at 5 VDC,
180 mA max. at 26 VDC
35 × 130 × 126 (W × H × D)
450 g max.
Conforms to general specifications for SYSMAC CS-series Series.
CS-series CPU Rack or CS-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.)
Depends on the Power Supply Unit. *3
Special I/O Unit Area
CIO 200000 to CIO 295915
(Words CIO 2000 to CIO 2959)
Internal Special I/O Unit DM Area
(D20000 to D29599)
4
1 to 5 V/4 to 20 mA
0 to 5 V
0 to 10 V
−10 to 10V
0.5 Ω max. (for voltage output)
12 mA (for voltage output)
600 Ω (current output) *9
4,000 (full scale)
16-bit binary data
23±2°C:
0°C to 55°C: Voltage output: ±0.5% of full scale
1.0 ms/point max.
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
When the Conversion Enable Bit is OFF. *8
In adjustment mode, when a value other than the output number is output during adjustment.
When there is an output setting error or a fatal error occurs at the PLC.
When the CPU Unit is on standby.
When the Load is OFF.
CS1W-DA041
Voltage output: ±0.3% of full scale
Current output: ±0.5% of full scale
Current output: ±0.8% of full scale
2 Units max.
5 Units max.
CS1W-DA08C
CPU Unit to Analog Output Unit
Analog Output Unit to CPU Unit
CPU Unit to Analog Output Unit
130 mA max. at 5 VDC,
180 mA max. at 26 VDC
8
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
CS1W-DA08V
Analog output setting data
Conversion Enable Bit
Alarm flags
Output signal conversion enable/disable,
output signal range setting
Output status for output hold
CS1W-AD/DA/MAD
130 mA max. at 5 VDC,
250 mA max. at 26 VDC
8
4 to 20 mA
600 Ω (current output) *8
CS1W-DA08C
9