SU3000XLNAFTA Tripp Lite, SU3000XLNAFTA Datasheet - Page 5

no-image

SU3000XLNAFTA

Manufacturer Part Number
SU3000XLNAFTA
Description
UPS TRUEONLINE 3.0KVA 2400W 9OUT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
UPSr
Datasheet

Specifications of SU3000XLNAFTA

Power - Rated
3kVA / 2400W
Ac Outlets
9 (UPS)
Features
DB9 and USB Communications, Rack Mount
Backup Time - Max Load
6 minutes
Media Lines Protected
1 - RJ45 Line
Voltage - Output Per Connector
120V (4 NEMA 5-15R, 4 NEMA 5-15/20R and 1 NEMA L5-30R)
Voltage - Input
208V / 30A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA L5-30P
Connector - Ac Output
4 NEMA 5-15R, 4 NEMA 5-15/20R and 1 NEMA L5-30R
Size
20.50" L x 9.00" W x 10.25" H (520.7mm x 228.6mm x 260.4mm)
Weight
69 lbs (31.3kg)
Ac Output Connector
4 NEMA 5-15R, 4 NEMA 5-15/20R and 1 NEMA L5-30R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
ENVIRONMENTAL
Operating Temperature
Range
Storage Temperature
Range
Relative Humidity
AC mode BTU / hr. (full
load)
AC economy mode
BTU / hr. (full load)
Battery mode BTU / hr.
(full load)
AC economy mode
efficiency rating (100%
load)
Audible Noise
COMMUNICATIONS
Communications
interface
Network monitoring
port description
PowerAlert software
Communications cable
WatchDog compatibility
LINE / BATTERY TRANSFER
Transfer time
Low voltage transfer to
battery power (setpoint)
High voltage transfer to
battery power (setpoint)
SPECIAL FEATURES
Cold Start (startup in
battery mode during a
power failure)
High availability UPS
features
Green & high efficiency
features
CERTIFICATIONS
UPS Certifications
WARRANTY
Product Warranty
Period (U.S., Canada &
Puerto Rico)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
1112.7
520.9
1219.3
94%
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
Included
USB and DB9 cabling included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
No transfer time (0 ms.) in online, double-conversion mode
175V (100% load), 80V (
138
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of
economy mode operation
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A
(EMI)
2-year limited warranty