ZUP10-20/U TDK Corporation, ZUP10-20/U Datasheet - Page 37

PWR SUP BENCH PROG 0-10V 200W

ZUP10-20/U

Manufacturer Part Number
ZUP10-20/U
Description
PWR SUP BENCH PROG 0-10V 200W
Manufacturer
TDK Corporation
Series
ZUPr
Type
Enclosedr
Datasheets

Specifications of ZUP10-20/U

Number Of Outputs
1
Efficiency
77%
Voltage - Output
0 ~ 10V
Power (watts)
200W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 10 VDC @ 20A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
200W
Operating Temperature
0°C ~ 50°C
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Output Current (max)
20A
Input Voltage
85 to 265V
Output Power (max)
200W
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Accuracy
0.02% + 8 mV
Brand/series
ZUP
Current, Output
20 A
Display Type
Digital Meter
Power, Output
200 W
Power, Rating
200 W (Max.)
Regulation, Line
0.01% + 2 mA⁄1 mV + 0.005%
Regulation, Load
0.01% + 5 mA⁄2 mV + 0.005%
Standards
UL Listed, CE Marked
Temperature Coefficient
30 ppm⁄°C (CV)⁄100 ppm⁄°C (CC)
Temperature, Operating, Maximum
50 °C
Temperature, Operating, Minimum
0 °C
Voltage, Input
85-265 VAC
Voltage, Noise
50 mV @ 20 MHz BW
Voltage, Output
10 VDC
Voltage, Ripple
5 mV @ 5 Hz to 1 MHz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1668
Q1074270
ZUP10-20/U
ZUP1020/U
4. OUTPUT VOLTAGE PROGRAMMING BY EXTERNAL RESISTOR
Fig 4-5 shows a typical set-up for programming the output voltage. A variable programming resistor,
0~4Kohm produces a proportional output voltage from zero to full scale. In order to set the low limit, a
series resistor can be connected to the programming resistor. For example; a 1kohm series resistor will
set the lower limit to 25% of full scale. In order to set the upper limit, a resistor can be connected in
parallel to the programming resistor. The resultant programming resistance of the series/parallel
resistors must be between 0 and 4Kohm.
Fig. 4-5:
Constant voltage resistive programming.
Fig. 4-6:
Constant current resistive programming.
5.OUTPUT CURRENT PROGRAMMING BY EXTERNAL RESISTOR
Fig 4-6 shows the set-up for constant current resistive programming. The explanation given for
constant voltage resistive programming also applies for constant current.
Resistive programming is possible for local and remote sensing.
sets lower
sets lower
Optional
Optional
limit
limit
programming resistor
programming resistor
0~4K
0~4K
NOTE
sets upper limit
sets upper limit
Optional
Optional
VCVP
VCCP
RCCP
COM
VCVP
VCCP
RCCP
External control connector
External control connector
- S
+S
COM
P
(ZUP rear panel view)
(ZUP rear panel view)
- S
+S
P
14
14
2
2
13
1
13
1
Output Good
Output Good
On/Off
VRFV
VRFI
RCVP
On/Off
VRFV
VRFI
RCVP
- LS
+LS
- LS
+LS

Related parts for ZUP10-20/U