2866475 Phoenix Contact, 2866475 Datasheet - Page 12

no-image

2866475

Manufacturer Part Number
2866475
Description
POWER SUPPLY 5A 12VDC
Manufacturer
Phoenix Contact
Series
Trior
Type
Industrialr
Datasheets

Specifications of 2866475

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 5A
Size / Dimension
4.53" L x 1.26" W x 5.12" H (115mm x 32mm x 130mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
60W
Efficiency
83%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
60 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
12 V
Output Current (channel 1)
5 A
Mounting Style
DIN Rail
Brand/series
TRIO
Configuration
Enclosed
Operation
Switching
Output
12 VDC @ 5 A
Phoenix Part Number
TRIO-PS/1AC/12DC/5
Power, Output
60 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
12 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2146
TRIO-PS/1AC/12DC/5
103347_en_00
15
I
0
U
N
N
Function
0
20
40
Ambient temperature [°C]
I
60
N
I
OUT
[A]
Output characteristic curve
The device functions following the U/I characteristic curve.
Under load, the working point follows this curve. The output
current is limited in the event of a short circuit or overload.
Thereby, the device does not switch off, but rather supplies a
continuous output current.
The secondary voltage is reduced until the short circuit or
overload on the secondary side has been remedied. The U/I
characteristic curve ensures that both heavily capacitive
loads and loads with DC/DC converters in the primary circuit
can be supplied. Downstream fuses are triggered. Selectivity
in the design of your system is guaranteed at all times.
U
I
P
Thermal behavior
With an ambient temperature of up to +55°C, the device
supplies the continuous output current of I
ambient temperatures above +55°C, the output current must
be reduced by 2.5% per Kelvin increase in temperature. The
device does not switch off at ambient temperatures of +70°C
or thermal overload. The output capacity is reduced as far as
necessary to provide device protection. After it has cooled
down, the output capacity is increased again.
Parallel operation
Devices of the same type can be connected in parallel to
enable both redundancy and an increase in efficiency. No
other alignment is necessary when in the state of delivery.
If the output voltage is adjusted, a uniform distribution of
power is guaranteed by setting all parallel operated power
supply units to exactly the same output voltage.
To ensure symmetrical distribution of power, we recommend
designing all cable connections from the power supply unit to
a busbar of the same length and with the same conductor
cross section. The system makes it advisable to install a
protective circuit at the output of each device when more than
two power supply units are connected in parallel (e.g.
decoupling diode or DC fuse). This prevents high reverse
feed currents in the event of a secondary device fault.
N
N
N
= 5 A
= 60 W
= 12 V
TRIO-PS/1AC/12DC/5
PHOENIX CONTACT
N
. In the case of
12

Related parts for 2866475