2866475 Phoenix Contact, 2866475 Datasheet - Page 9

no-image

2866475

Manufacturer Part Number
2866475
Description
POWER SUPPLY 5A 12VDC
Manufacturer
Phoenix Contact
Series
Trior
Type
Industrialr
Datasheets

Specifications of 2866475

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 5A
Size / Dimension
4.53" L x 1.26" W x 5.12" H (115mm x 32mm x 130mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
60W
Efficiency
83%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
60 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
12 V
Output Current (channel 1)
5 A
Mounting Style
DIN Rail
Brand/series
TRIO
Configuration
Enclosed
Operation
Switching
Output
12 VDC @ 5 A
Phoenix Part Number
TRIO-PS/1AC/12DC/5
Power, Output
60 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
12 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2146
TRIO-PS/1AC/12DC/5
103347_en_00
10
11
The connection for 100 V AC ... 240 V AC is made using the L, N and PE screw connections.
The device can be connected to 1-phase AC networks or to two of the phase conductors of 3-phase networks (TN, TT or IT
networks in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC.
In the case of input voltages > 300 V AC, the device switches off for its own safety. After the overvoltage has ceased, the
device starts automatically within a few seconds.
For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided.
L
A
N
A
Mounting on DIN rails
Connection to various systems
TN-S
PE
ATTENTION: Module can become damaged
In order to comply with the UL certification, use copper cables that are designed for operating temperatures of
> 75°C.
In order to comply with EN 60950/UL 60950, flexible cables require ferrules. To safely connect a device, the
ferrules should have a length of at least 10 mm. To achieve a reliable and shockproof connection, strip the
connecting ends according to section "Structure".
+
-
L
N
PE
L
B
N
TN-C
PE
+
-
B
L
PEN
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
L
N
PE
TT
+
-
L
N
TRIO-PS/1AC/12DC/5
L
PHOENIX CONTACT
N PE
iT
+
-
L1
L2
L3
9

Related parts for 2866475