E8Y-A5Y-R Omron, E8Y-A5Y-R Datasheet - Page 5

no-image

E8Y-A5Y-R

Manufacturer Part Number
E8Y-A5Y-R
Description
SENSOR PRESSURE DIFF 0-5KPA NPN
Manufacturer
Omron
Series
E8Yr
Datasheet

Specifications of E8Y-A5Y-R

Pressure Type
Differential
Operating Pressure
0.73 PSI, 5 kPa
Port Size
Male, 1/8" (3.175mm) Pipe Threads
Output
Digital
Voltage - Supply
12 V ~ 24 V
Termination Style
Cable
Operating Temperature
-10°C ~ 55°C
Package / Case
Module
Mounting Style
Screw
Maximum Operating Temperature
+ 55 C
Minimum Operating Temperature
- 10 C
Operating Supply Voltage
15 V, 18 V
Output Voltage
30 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E8YA5YR
E8Y
Functions Table - continued from previous page
Function
Auto-teaching
(continued)
Key-protect
Set value
zero-setting
Speed control
function with
measured
pressure display
Error display
(Set value lock
function)
Description
(2) 1-point auto-teaching (Window mode teaching)
This function automatically sets the ON point and OFF point for the comparitive output by inputing a reference
point (TEACH 1) using an actual object. The function operates only when an object exists. The outputs are
made in the window mode. The hysteresis width and window width are set values. (The window width set value
is valid only when 1-point teaching is set. Setting range: (0 to rated value) x 30%)
The ON point and OFF point set values are set at the reference point window width.
Example: If the reference point (TEACH 1) is 0.90 kPa and the window width is 0.50 kPa,
the ON set value = (0.90 - 0.50)/2 = 0.20 and the OFF point set value = (0.90+0.50)/2 = 0.70.
This function restricts switch operation to prevent the set value from being easily changed.
Set value: OFF <> ON
Hold down the ADJ key for several seconds in the measurement mode to activate this function.
Select from three values of display speed for the measured pressure values. Set value: 0.1 s, 0.5 s, 1.0 s
(1) Pressure warning during zeroing:
Error display and warning if excess pressure or flow (exceeding rated value 5%) is applied during zeroing.
(2) Teaching error display:
Warning if teaching is unsuccessful.
(3) Short-circuit protection and display:
If overcurrent flows in a connected load, the abnormal status is notified by an error display and the OUT LED,
for the corresponding output, flashing. Transistor acts to cut the abnormal current.
(4) Abnormal pressure or flow detection:
The diplayed value flashes to indicate the abnormal status if the applied pressure or flow exceeds the rated
value by 10%. This error is automatically reset when the supplied value enters the rated range.
(5) ON/OFF point input error warning:
Indicates if the difference between the ON point and OFF point in the window mode exceeds the hysteresis
value + setting resolution (0.01 kPa/1 mmH
Output
ON
OFF
Hysteresis width
0
Window width
ON
point
Standard
value
(TEACH 1)
Window width
Hysteresis width
OFF
point
Pressure value
2
O).
6
E8Y