LC1D09BD SQUARE D, LC1D09BD Datasheet - Page 63

no-image

LC1D09BD

Manufacturer Part Number
LC1D09BD
Description
CONTACTOR, 3PST-NO, 24VDC, 20A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09BD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Voltage Ac Max
600V
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
01/04
LR2K0301
LA7K0064
Selection of Type LR\bK Overload Relays
These overload relays are designed for the protection of motors. They are ambient-compensated and
phase-failure sensitive. They may be reset either manually or automatically.
For direct mounting, the relays are placed under the contactors with screw clamp terminals only
(pre-wired terminals; see page 64). For separate mounting, use terminal block LA7K0064 (see below).
The front face of the overload relay provides:
• Selection of reset mode: Manual (marked H) or Automatic (marked A).
• A red pushbutton for the Trip Test function.
• A blue pushbutton for Stop and manual reset.
• A yellow trip flag to indicate that the overload relay tripped.
Three-Pole Overload Relays with Screw Clamp Terminals
Overload Relays without Single-phase Sensitivity f
Accessory
Short-circuit protection for
North American applications
Relay Setting
Range
A
Class 10 (the standard specifies a tripping time of between 2 and 10 seconds at 7.2 In)
0.11 to 0.16
0.16 to 0.23
0.23 to 0.36
0.36 to 0.54
0.54 to 0.8
0.8 to 1.2
1.2 to 1.8
1.8 to 2.6
2.6 to 3.7
3.7 to 5.5
5.5 to 8
8 to 11.5
10 to 14
12 to 16
f
Class 10: To order, replace the prefix LR2 by LR7 in the catalog numbers selected from above (only applicable to overload relays LR2K0305
to LR2K0322). Example: LR7K0308.
f
Description
Terminal block for separate clip-on mounting
of the overload relay on 35 mm DIN rail
Not UL Listed or CSA Certified.
Not UL Listed or CSA Certified.
European type fuses
Maximum rating
Type
aM
A
0.25
0.25
0.5
1
1
2
2
4
4
6
8
10
16
20
By circuit breaker
By fuses
gl
A
0.5
0.5
1
1.6
2
4
6
8
10
16
20
25
32
40
Type of Connection
Screw clamp
BS88
A
6
6
10
16
16
20
20
25
32
Selection of Type LR•K Overload Relays
©
2001-2004 Schneider Electric All Rights Reserved
Select in accordance with NEC and local codes
Maximum 400% of motor FLA
Catalog Number
LR2K0301
LR2K0302
LR2K0303
LR2K0304
LR2K0305
LR2K0306
LR2K0307
LR2K0308
LR2K0310
LR2K0312
LR2K0314
LR2K0316
LR2K0321 f
LR2K0322 f
Catalog Number
LA7K0064
Weight lb. (kg)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
0.32 (0.145)
Weight lb. (kg)
0.22 (0.100)
63

Related parts for LC1D09BD