LC1D09BD SQUARE D, LC1D09BD Datasheet - Page 84

no-image

LC1D09BD

Manufacturer Part Number
LC1D09BD
Description
CONTACTOR, 3PST-NO, 24VDC, 20A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09BD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Voltage Ac Max
600V
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Characteristics of Type LC•D and LP•D Contactors
84
DC Control Circuit Characteristics
Type of contactor
Rated control circuit voltage (Uc)
Rated insulation voltage
Control voltage limits
Average consumption at 20 °C (68 ° F)
and at Uc
Average operating time at Uc (1)
Time constant (L/R)
Mechanical life at Uc
Maximum operating rate
at ambient temperature 60 °C (140 °F)
Low Consumption Control Circuit Characteristics
Rated insulation voltage
Maximum voltage
Average consumption dc
at 20 °C and at Uc
Operating time (1) at Uc and
at 20 °C (68 ° F)
Voltage limits
of the control circuit
Time constant (L/R)
Mechanical life
Maximum operating rate
Rated insulation voltage
(1)
Operating times depend on the type of contactor electromagnet and its control mode.
The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time “O” is measured from the moment the coil supply is
switched off to the moment the main poles separate.
©
2001-2004 Schneider Electric All Rights Reserved
60 °C (140 °F)
dc
Conforming to IEC 60947-1
Conforming to UL, CSA
Operational
Drop-out
dc
Closing
Opening
Note: The arcing time depends on the circuit switched by the poles. For normal three-phase applications, the arcing time is usually less than 10 ms.
The load is isolated from the supply after a time equal to the sum of the opening time and the arcing time.
In millions of operating cycles
In operating cycles per hour
Conforming to IEC 60947-1
Conforming to UL, CSA
Of the control circuit on dc
Wide range coil
(0.7 to 1.25 Uc)
Closing
Opening
Operational
Drop-out
In millions of operating cycles
At ambient temperature
Conforming to UL, CSA
Conforming to IEC 60947-1
Standard coil
Wide range coil
Inrush
Sealed
“C”
“O”
Inrush
Sealed
“C”
“O”
60 °C (140 °F)
V
V
V
W
W
ms
ms
ms
V
V
W
W
ms
ms
ms
V
V
ops/h
LC1
D09 to D38
DT20 to DT40
12 to 440
690
600
0.7 to 1.25 Uc
at 60 °C (140 °F)
0.1 to 0.25 Uc
at 60 °C (140 °F)
5.4
5.4
55
20
28
30
3600
690
600
250
2.4
2.4
70
25
0.7 to 1.25 Uc
0.1 to 0.3 Uc
40
30
3600
600
690
LP1
D12 and D25
0.8 to 1.1 Uc
@ 55 °C (131 °F)
0.7 to 1.25 Uc
@ 55 °C (131 °F)
9/11
9/11
52 - 64
8 - 14
42
30
3600
LC1 or LP1
D40 to D65
12 to 440
0.85 to 1.1 Uc
at 55 °C (131 °F)
0.75 to 1.2 Uc
at 55 °C (131 °F)
0.1 to 0.3 Uc at 55 °C (131 °F)
22
22
85 to 110
20 to 35
65
20
3600
LC1 or
LP1D80
22
22
95 to 130
20 to 35
75
20
3600
LC1D115 &
LC1D150
24 to 440
0.75 to 1.2 Uc
at 55 °C (131 °F)
0.15 to 0.4 Uc
at 55 °C (131 °F)
270 to 365
2.4 to 5.1
20 to 35
40 to 75
25
8
1200
01/04