3UG4633-1AL30 SIEMENS, 3UG4633-1AL30 Datasheet - Page 4

RELAY, DIGITAL MONITORING, VOLTAGE

3UG4633-1AL30

Manufacturer Part Number
3UG4633-1AL30
Description
RELAY, DIGITAL MONITORING, VOLTAGE
Manufacturer
SIEMENS
Series
3UGr
Datasheet

Specifications of 3UG4633-1AL30

Power Consumption
2W
Supply Voltage Max
275V
Relay Mounting
DIN Rail
Control Voltage Type
AC / DC
Contact Termination
Screw
External Depth
86mm
External Length / Height
110mm
External Width
22.5mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3UG Monitoring Relays for Electrical and Additional Measurements
Line monitoring
Technical specifications
1)
Rated control supply voltage U
Rated frequency
Rated power, typical
• At 230 V AC
• At 400 V AC
• At 460 V AC
Width
RESET
Principle of operation
Availability time after application of U
Response time on reaching a switching threshold
Adjustable tripping delay time
Adjustable ON-delay time
Mains buffering time, min.
Rated insulation voltage U
Degree of pollution 3
Overvoltage category III according to VDE 0110
Rated impulse withstand voltage
Permissible ambient temperature
• During operation
• During storage
EMC tests
Degree of protection
• Enclosures
• Terminals
Vibration resistance according to IEC 60068-2-6
Shock resistance according to IEC 60068 Part 2-27
Conductor cross-section
• Screw terminals
• Spring-loaded terminals
Measuring range AC 50/60 Hz rms value
Setting range
Measuring accuracy
Repeat accuracy at constant parameters
Setting accuracy
Accuracy of digital display
Deviations for temperature fluctuations
Hysteresis for voltage
Hysteresis for unbalance
Deviation for frequency fluctuation
General data
Measuring circuit
7/64
- Solid
- Finely stranded with end sleeve
- AWG conductors, solid or stranded
- Tightening torque
- Solid
- Finely stranded, with end sleeves according to
- Finely stranded
- AWG conductors, solid or stranded
Note: This is a Class A product. In the household environment this device
may cause radio interference. In this case the user must introduce suitable
measures.
DIN 46228
Monitoring Relays
1)
Siemens LV 1 T · 2007
i
s
s
V
Hz
W/VA
W/VA
W/VA
mm
ms
ms
s
s
ms
V
kV
°C
°C
Hz/mm 1-6/15; 6-500, 20 m/s
g/ms
mm
mm
AWG
Nm
mm
mm
mm
AWG
V
V
%
%
%/°C
V
%
%
2
2
2
2
2
3UG45 11-
..N20
160 … 260
50/60
2/4
--
--
22.5
Auto-RESET
Closed-circuit
200
Max. 450
--
--
10
690
6
-25 … +60
-40 … +85
IEC 60947-1/ IEC 61000-6-2 / IEC 61000-6-4
IP40
IP20
15/11
M3 (standard screwdriver size 2 and Pozidriv 2)
1 x (0.5 ... 4) / 2 x (0.5 ... 2.5)
1 x (0.5 ... 2.5) / 2 x (0.5 ... 1.5)
2 x (20 ... 14)
0.8 … 1.2
2 x (0.25 ... 1.5)
2 x (0.25 ... 1.5)
2 x (0.25 ... 1.5)
2 x (24 ... 16)
160 ... 260
--
--
--
--
--
--
--
--
© Siemens AG 2007
3UG45 11-
..P20
320 … 500
--
2/8
--
320 ... 500
2
3UG45 11-
..Q20
420 … 690
--
--
2/8
420 ... 690
3UG45 12
160 … 690
2/2.5
2/3.5
2/4
1000
30
160 ... 690
3UG45 13
Automatic/manual
0.1 ... 20
200...690
±5
±1
– 10 %
referred to
set value
±0.1
5 % of set
value
±1 %
3UG46 14
Closed-circuit, open-circuit
(3UG46 17/3UG46 18:
closed-circuit)
0.1 … 20
160...690
– 1 V
+/-1 digit
1 ... 20 V
2 % of limit
value
3UG46 15
3UG46 16
3UG46 17
3UG46 18
--
2 % of limit
value for
3UG46 17/
3UG46 18