H3YN-21 100-120VAC Omron, H3YN-21 100-120VAC Datasheet - Page 3

SOLID STATE TIMER, DPDT, 10H, 120VAC

H3YN-21 100-120VAC

Manufacturer Part Number
H3YN-21 100-120VAC
Description
SOLID STATE TIMER, DPDT, 10H, 120VAC
Manufacturer
Omron
Datasheet

Specifications of H3YN-21 100-120VAC

Contact Configuration
DPDT
Nom Input Voltage
120VAC
Delay Time Range
0.1min To 10h
Timing Adjustment
DIP Switch
Relay Mounting
Plug In
Supply Voltage Max
120VAC
No. Of Poles
2
Contact Carrying Power
14VA
Supply Voltage Min
100VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
■ Characteristics
Note: 1. Terminal screw sections are excluded.
Accuracy of operating time
Setting error
Reset time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Impulse withstand voltage
Noise immunity
Static immunity
Degree of protection
Weight
EMC
Approved standards
2. Refer to the Life-test Curve.
Item
±1% FS max. (1 s range: ±1%±10 ms max.)
±10%±50 ms FS max.
Min. power-opening time: 0.1 s max. (including halfway reset)
±2% FS max.
±2% FS max.
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts) (see note 1)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Destruction: 1,000 m/s
Malfunction: 100 m/s
Operating:
Storage:
Operating:
Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Destruction: 8 kV
Malfunction: 4 kV
IP40
Approx. 50 g
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference from AM Radio Waves:
Immunity Burst:
Immunity Surge:
UL508, CSA C22.2 No. 14, Lloyds
Conforms to EN61812-1 and IEC60664-1. (2.5 kV/2 for H3YN-2/-21, 2.5 kV/1 for H3YN-4/-41, H3YN-
4-Z/-41-Z)
Output category according to EN60947-5-1.
−10°C to 50°C (with no icing)
−25°C to 65°C (with no icing)
35% to 85%
DPDT:
500,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
4PDT:
200,000 operations min. (H3YN-4-Z/-41-Z: 100,000 operations min.)
(3 A at 250 VAC, resistive load at 1,800 operations/h) (see note 2)
2
2
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
EN61000-4-2: 8 kV air discharge (level 3)
EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
EN61000-4-5: 2 kV line to ground (level 3)
H3YN-2/-21/-4/-41
2 kV I/O signal-line (level 4)
1 kV line to line (level 3)
H3YN
3

Related parts for H3YN-21 100-120VAC