3RB2016-1SB0 SIEMENS, 3RB2016-1SB0 Datasheet

RELAY, OVERLOAD, 3-12A

3RB2016-1SB0

Manufacturer Part Number
3RB2016-1SB0
Description
RELAY, OVERLOAD, 3-12A
Manufacturer
SIEMENS
Datasheet

Specifications of 3RB2016-1SB0

Control Voltage Range
690V
Load Current
12A
Control Voltage Ac Max
690VAC
External Depth
73mm
External Length / Height
64mm
External Width
45mm
Operating Frequency Max
60Hz
Operating Frequency Min
50Hz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Overview
1)
2)
Features
Sizes
Seamless current range
Tripping in the event of overload
Tripping in the event of phase
unbalance
Tripping in the event of phase failure
Protection of single-phase loads
Tripping in the event of overheating
by
integrated thermistor motor
protection function
Tripping in the event of a ground fault
by
internal ground fault detection
(activatable)
RESET function
Remote RESET function
TEST function for auxiliary contacts
TEST function for electronics
Status display
Large current adjustment button
Integrated auxiliary contacts
(1 NO + 1 NC)
General data
Protection functions
Features
Motor currents up to 820 A can be recorded and evaluated by a current
measuring module, e.g. 3RB29 06-2BG1 (0.3 ... 3 A) , in combination with
a 3UF18 68-3GA00 (820 A / 1 A) series transformer.
The SIRIUS 3RN thermistor motor protection devices can be used to
provide additional protection temperature-dependent protection.
Benefits
• Are coordinated with the dimensions, connections
• Permit the mounting of slim and compact load
• Simplify configuration
• Allows easy and consistent configuration with one
• Provides optimum inverse-time delayed protection
• Provides optimum inverse-time delayed protection
• Minimizes heating of induction motors during
• Enables the protection of single-phase loads
• Provides optimum temperature-dependent pro-
• Eliminates the need for additional special
• Saves space in the control cabinet
• Reduces wiring outlay and costs
• Provides optimum protection of loads against
• Eliminates the need for additional special
• Saves space in the control cabinet
• Reduces wiring outlay and costs
• Allows manual or automatic resetting of the relay
• Allows the remote resetting of the relay
• Allows easy checking of the function and wiring
• Allows checking of the electronics
• Displays the current operating status
• Makes it easier to set the relay exactly to the
• Allows the load to be switched off if necessary
• Can be used to output signals
and technical characteristics of the other devices
in the SIRIUS modular system (contactors, soft
starters, ...)
feeders in widths of 45 mm (S00), 45 mm (S0),
55 mm (S2), 70 mm (S3), 120 mm (S6) and
145 mm (S10/S12)
series of overload relays (for small to large loads)
of loads against excessive temperature rises due
to overload
of loads against excessive temperature rises due
to phase unbalance
phase failure
tection of loads against excessive temperature ris-
es, e.g. for stator-critical motors or in the event of
insufficient coolant flow, contamination of the mo-
tor surface or for long starting or braking opera-
tions
equipment
high-resistance short-circuits or ground faults due
to moisture, condensed water, damage to the in-
sulation material, etc.
equipment.
correct current value
© Siemens AG 2007
3RU11
S00 ... S3
0.11 ... 100 A
(by means of sepa-
rate module)
( )
--
--
--
2)
Overload Relays
3RB20/3RB21
S00 ... S12
0.1 ... 630 A
(only 3RB21 with
(only 3RB21)
24 V DC)
Siemens LV 1 · 2007
--
--
2)
3RB22/3RB23
S00 ... S12
0.3 ... 630 A
( ... 820 A)
General data
(2 ×)
1)
5/31

Related parts for 3RB2016-1SB0

3RB2016-1SB0 Summary of contents

Page 1

... Siemens AG 2007 Overload Relays 3RU11 3RB20/3RB21 S00 ... S3 S00 ... S12 0.11 ... 100 A 0.1 ... 630 (by means of sepa- (only 3RB21 with rate module) -- General data 3RB22/3RB23 S00 ... S12 0.3 ... 630 ... 820 (only 3RB21 DC) (2 ×) Siemens LV 1 · 2007 5/31 ...

Page 2

... Direct mounting to contactor saves space, even for high motor currents (i.e. no heat decoupling is required). 1) Exception size S3, only stand-alone installation is possible. 2) Alternatively available for screw terminals. 5/32 Siemens LV 1 · 2007 © Siemens AG 2007 3RU11 3RB20/3RB21 -- (S00 ...

Page 3

... Saves space in the control cabinet • Reduces wiring outlay and costs 1) The SIRIUS 3RU11 thermal overload relays use a bimetal contactor and therefore do not require a control supply voltage. © Siemens AG 2007 Overload Relays 3RU11 3RB20/3RB21 General data 3RB22/3RB23 -- (only 3RB21 Siemens LV 1 · 2007 5/33 ...

Page 4

... When using the overload relays with trip class ≥ CLASS 20, see Technical Specifications, Short-Circuit Protection with Fuses for Motor Feeders and the configuring aid "Configuring SIRIUS Fuseless Load Feeders". 5/34 Siemens LV 1 · 2007 © Siemens AG 2007 Current Contactors (type, size, rating in kW) ...

Page 5

... They comply with all important worldwide standards and approvals. Benefits The most important features and benefits of the 3RB20/3RB21 solid-state overload relays are listed in the overview table Overload Relays, General Data). (see Curves). (see (see Siemens LV 1 · 2007 5/35 ...

Page 6

... A 100 % 3RB20 66/3RB21 66 160 ... 630 A 100 % 5/36 Siemens LV 1 · 2007 © Siemens AG 2007 "Increased safety" type of protection EEx e according to ATEX directive 94/9/EC The 3RB20/3RB21 solid-state overload relays are suitable for the overload protection of explosion-proof motors with "increased safety" type of protection EEx e. The relays meet the require- ments of EN 60079-7 (Electrical apparatus for potentially explo- sive atmospheres – ...

Page 7

... Setting range in A 0.1 ... 0.4 0.32 ... 1.25 1 ... 4 3 ... 12 1 ... 4 3 ... 12 6 ... 25 6 ... 25 12.5 ... 50 12.5 ... 50 25 ... 100 50 ... 200 55 ... 250 160 ... 630 Siemens LV 1 · 2007 5/37 ...

Page 8

... The relays with an Order No. ending with "1" are designed for stand-alone installation. 4) Observe maximum rated operational current of the devices. 5/38 Siemens LV 1 · 2007 © Siemens AG 2007 • Manual and automatic RESET • Switch position indicator • TEST function and self-monitoring ...

Page 9

... Siemens LV 1 · 2007 5/39 ...

Page 10

... The relays with an Order No. ending with "1" are designed for stand-alone installation. 4) Observe maximum rated operational current of the devices. 5/40 Siemens LV 1 · 2007 © Siemens AG 2007 • Manual and automatic RESET • Switch position indicator • TEST function and self-monitoring ...

Page 11

... Siemens LV 1 · 2007 5/41 ...

Page 12

... The relays with an Order No. ending with "1" are designed for stand-alone installation. 4) Observe maximum rated operational current of the devices. 5/42 Siemens LV 1 · 2007 © Siemens AG 2007 • Manual and automatic RESET • Electrical remote RESET integrated • Switch position indicator • ...

Page 13

... Siemens LV 1 · 2007 5/43 ...

Page 14

... Enables more functions to be added, e.g. internal ground fault detec- tion and/or an analog output with corresponding signals. 3RB29 06 current measuring module 5/44 Siemens LV 1 · 2007 © Siemens AG 2007 The modular, solid-state overload relays with external power supply type 3RB22 (with monostable auxiliary contacts) and ...

Page 15

... Box terminal blocks for the current measuring modules size S6 and S10/S12 • Terminal covers for the current measuring modules size S6 and S10/S12 • Push-in lugs for screw mounting the size S00 to S3 current measuring modules Siemens LV 1 · 2007 5/45 ...

Page 16

... Use 3RB29 87-2D connecting cable. 3) Motor currents up to 820 A can be recorded and evaluated by a current measuring module, e.g. 3RB29 06-2BG1 (0.3 ... combination with a 3UF18 68-3GA00 (820 series transformer. 5/46 Siemens LV 1 · 2007 © Siemens AG 2007 Replacement type Current measuring module Setting range in A 3RB29 ...

Page 17

... Price PU PS* PG Weight per PU (UNIT, per PU SET, M) approx unit 101 0.030 1 1 unit 101 0.030 1 1 unit 101 0.030 1 1 unit 101 0.030 1 1 unit 101 0.030 I the unit e I the unit e Siemens LV 1 · 2007 5/47 ...

Page 18

... S00 ... S3 • Length 0.1 m (only for mounting of the evaluation module directly onto the current measuring module) S00 ... S12 • Length 0.5 m 3RB29 87-2. 5/48 Siemens LV 1 · 2007 © Siemens AG 2007 1) 1)2) and stand-alone installation Set current value Short-circuit DT Order No ...

Page 19

... Overload Relays Accessories Price PU PS* PG Weight (UNIT, per PU SET, M) approx unit 101 0.060 1 1 unit 101 0.080 1 1 set 101 0.038 1 1 unit 102 0.021 1 1 unit 102 0.004 1 1 unit 101 0.063 1 1 unit 101 0.073 Siemens LV 1 · 2007 5/49 ...

Page 20

... For more accessories (tools for spring-loaded terminals and labeling plates), see page 5/56. 1) Only for 3RB20/3RB21. The accessories are identical to those of the 3RU11 thermal overload relays the scope of supply for 3RT10 54-1 contactors (55 kW). 5/50 Siemens LV 1 · 2007 © Siemens AG 2007 Size DT Order No. Price } S00 ... 3RB29 84-0 S10/S12 – ...