E5CN-R2MTD-500 ACDC24 Omron, E5CN-R2MTD-500 ACDC24 Datasheet - Page 10

Digital Temperature Controller

E5CN-R2MTD-500 ACDC24

Manufacturer Part Number
E5CN-R2MTD-500 ACDC24
Description
Digital Temperature Controller
Manufacturer
Omron
Datasheet

Specifications of E5CN-R2MTD-500 ACDC24

Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.3%
Output Voltage Max
240VAC
Output Voltage Min
5V
Controller Input
Thermocouple Or RTD
Thermocouple Type
J, K, T, E, L, U, N, R, S, B, W, PLII
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
USB-Serial Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
Communications Specifications
* The baud rate, data bit length, stop bit length, and vertical parity can
Applicable OS
Applicable software
Applicable models
USB interface standard Conforms to USB Specification 1.1.
DTE speed
Connector
specifications
Power supply
Power supply voltage
Current consumption
Ambient operating
temperature
Ambient operating
humidity
Storage temperature
Storage humidity
Altitude
Weight
Transmission line
connection method
Communications
Synchronization
method
Protocol
Baud rate
Transmission code ASCII
Data bit length *
Stop bit length *
Error detection
Flow control
Interface
Retry function
Communications
buffer
Communications
response wait time
be individually set using the Communications Setting Level.
installation information in the operation manual for the
Conversion Cable.
RS-485: Multipoint
RS-485 (two-wire, half duplex)
Start-stop synchronization
CompoWay/F, SYSWAY, or Modbus
1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
None
RS-485
None
217 bytes
0 to 99 ms
Default: 20 ms
Windows 2000, XP, or Vista
CX-Thermo version 4 or higher
E5AN/E5EN/E5CN/E5CN-U/E5AN-H/
E5EN-H/E5CN-H/E5GN
38400 bps
Computer: USB (type A plug)
Temperature Controller: Setup Tool port
(on bottom of Controller)
Bus power (Supplied from USB host
controller.)
5 VDC
70 mA
0 to 55°C (with no condensation or icing)
10% to 80%
−20 to 60°C (with no condensation or
icing)
10% to 80%
2,000 m max.
Approx. 100 g
Current Transformer (Order Separately)
Ratings
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
*1. For heater burnout alarms, the heater current will be measured
*2. For SSR failure alarms, the heater current will be measured when
*3. For heater overcurrent alarms, the heater current will be
Electrical Life Expectancy Curve for
Relays (Reference Values)
Note: Do not connect a DC load to a Controller with a Long-life Relay
Dielectric strength
Vibration resistance 50 Hz, 98 m/s
Weight
Accessories
(E54-CT3 only)
CT input
(for heater current
detection)
Maximum heater current 50 A AC
Input current indication
accuracy
Heater burnout alarm
setting range *1
SSR failure alarm
setting range *2
Heater overcurrent
alarm setting range *3
500
300
100
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
50
30
10
5
3
1
0
Output.
E5CN
250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
2
1,000 VAC for 1 min
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Armatures (2)
Plugs (2)
3
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
±5% FS ±1 digit max.
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
Switching current (A)
4
5
2
E5CN/E5CN-U
6
10

Related parts for E5CN-R2MTD-500 ACDC24