T4810000 Red Lion Controls, T4810000 Datasheet - Page 6

Process/Temperature Controller

T4810000

Manufacturer Part Number
T4810000
Description
Process/Temperature Controller
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheet

Specifications of T4810000

Operating Temperature Max
50°C
Operating Temperature Min
0°C
Temperature Accuracy ±
0.3%
Output Voltage Max
250VAC
Output Voltage Min
30VDC
Controller Input
Thermocouple Or RTD
Brand/series
T48 Series
Contact Form
SPST
Current, Load
1 A @ 35 °C (Max.)
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Temperature, Ambient
0 to +50 °C (Max.)
Termination
Screw
Voltage, Rating
120⁄240 VAC
Voltage, Supply
85 to 250 VAC
Panel Cutout
1.77" × 1.77" (1⁄16 DIN)
Power Requirements
85-250 VAC
Sealing
NEMA 4X/IP65
Operating Temperature
0°C to +50°C
Thermocouple Type
J, K, T, E, R, S, B, N, Linear MV
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
MULTIPLE UNIT STACKING
stacked either horizontally or vertically. For vertical stacking, install the panel
latch with the screws to the sides of the unit. For horizontal stacking, the panel
latch screws should be at the top and bottom of the unit. The minimum spacing
from center line to center line of units is 1.96" (49.8 mm). This spacing is the
same for vertical or horizontal stacking.
Note: When stacking units, provide adequate panel ventilation to ensure that
ACCESSORY - CURRENT TRANSFORMER-50 A
equipped with the Heater Current Monitor.
PANEL LATCH INSTALLED FOR
The T48 is designed for close spacing of multiple units. Units can be
the maximum operating temperature range is not exceeded.
The external Current Transformer is used when specifying the T48s
Part Number: CT005001
Current Ratio: 50 : 0.1 (Amperes)
Operation Frequency: 50 to 400 Hz
Insulation Class: 0.6 KV BIL, 10 KV full wave.
Terminals: Brass studs No. 8-32 UNC with flat washer and hex nuts.
Window Diameter: 1.13" (28.7 mm)
Weight: 8 oz (226.0 g)
VERTICAL UNIT STACKING
PANEL CUT-OUT SPACING FOR MULTIPLE UNIT STACKING.
HORIZONTAL ARRANGEMENT SHOWN.
PANEL LATCH INSTALLED FOR
HORIZONTAL UNIT STACKING
6
ACCESSORY - EXTERNAL SSR POWER UNIT
Drive outputs to switch loads up to 240 VAC @ 45 Amps, 25°C ambient. The
unit is operated by applying a low level DC control signal to the isolated
input. The unit features zero cross detection circuits which reduces radiated
RFI when switching load currents. With no contacts to wear out, the SSR
Power Unit provides virtually limitless operational life. The unit is supplied
with an integral heat sink for immediate installation.
External SSR Power Unit:
ACCESSORY - CURRENT TRANSFORMER-40 A
equipped with the Heater Current Monitor.
Current Transformers:
The external SSR Power Unit is used with T48s equipped with Logic/SSR
Part Number: RLY50000
Switched Voltage Range: 50 to 280 VAC
Load Current: 45 Amps max. @ 25°C ambient temperature
On State Input: 3 to 32 VDC @ 1500 Ω impedance. (isolated)
Off State Input: 0.0 to 1.0 VDC
Size: 5.5" (14 cm) L x 4.75" (12 cm) W x 2.62" (6.6 cm) H
The external Current Transformer is used when specifying the T48s
Part Number: CT004001
Current Ratio: 40 : 0.1 (Amperes)
Max Heater Current: 50 A
Dielectric Strength: 1000 VAC (For 1 minute)
Vibration Resistance: 50 Hz (Approx 10 G)
Terminals: Solder Type
Window Diameter: 0.228" (5.8 mm)
Weight: 0.406 oz (11.5 g)
35 Amps max. @ 50°C ambient temperature
(Use Logic/SSR drive output.)

Related parts for T4810000