SI-LS100MRFF BANNER ENGINEERING, SI-LS100MRFF Datasheet - Page 5

SWITCH, SAFETY INTERLOCK, 2NC/1NO, 10A

SI-LS100MRFF

Manufacturer Part Number
SI-LS100MRFF
Description
SWITCH, SAFETY INTERLOCK, 2NC/1NO, 10A
Manufacturer
BANNER ENGINEERING
Type
Interlockr
Datasheets

Specifications of SI-LS100MRFF

Contact Configuration
3PST-2NC / 1NO
Contact Voltage Ac Max
230V
Contact Voltage Dc Max
24V
Contact Current Ac Max
10A
Contact Current Dc Max
6A
Circuitry
3PST-2NC/1NO
Actuator Type
Flexible
Contact Form
1 NO, 2 NC
Current, Rating
10/6 AAC/ADC
Function
Safety
Ip Rating
IP65
Number Of Positions
3
Standards
UL Listed, CSA Certified, CE Marked
Temperature Rating
-30 to +80 °C
Voltage, Rating
230/24 VAC/VDC
Peak Reflow Compatible (260 C)
No
Lead Free Status / Rohs Status
RoHS Exempt Product
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Machine Safety Switches –
We recommend that safety switches be checked at each shift change or machine setup
by a designated person (see below) for:
1. Breakage of the switch body or actuator,
2. Good alignment and full engagement of the actuator with the receptor,
3. Confirmation that the safety switch is not being used as an end stop,
4. Loosening of the switch or actuator mounting hardware, and
5. Verification that it is not possible to reach any hazard point through an opened guard
In addition, we recommend that a qualified person check for the following on a periodic
schedule determined by the user based upon the severity of the operating environment
and the frequency of switch actuations:
1. Check the wiring chamber for signs of contamination.
2. Check the contacts for signs of deterioration or damage.
3. Inspect the electrical wiring for continuity and damage.
4. Verify that wiring conforms to the instructions on pages 3 and 4 of this data sheet.
A designated person is identified in writing by the employer as being appropriately trained
to perform a specified checkout procedure. A qualified person possesses a recognized
degree or certificate or has extensive knowledge, training, and experience to be able to
solve problems relating to the safety switch installation (ANSI B30.2).
Do not attempt any repairs to the switch. It contains no field-replaceable
components. Return the switch to the factory for warranty repair or replacement.
If it ever becomes necessary to return a switch to the factory, please do the following:
1. Contact the Banner applications engineering department at the number or address
2. Pack the switch carefully. Damage which occurs in shipping is not covered by
(or any opening) before hazardous machine motion has completely stopped.
listed on the front cover. They will attempt to troubleshoot the system from your
description of the problem. If they conclude that a component is defective, they will
issue an RMA (Return Merchandise Authorization) number for your paperwork, and
give you the proper shipping address.
warranty.
Periodic Checks
Repairs
SI-LS83 and SI-LS100 Series
P/N 59622 rev. E
5